FIR04-00185
| INSP-Final Inspection | 5/20/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | A | PASS |
|
|
Contact: Mike; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR04-00141
| INSP-Sprinkler Rough-in/Hydro | 5/20/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | A | FAIL |
|
|
Contact: Charles -- 200 lb test, please come after 10am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley FDC hydro didn't hold pressure 5/21/2004 11:24:19 AM
|
FIR04-00069
| INSP-Final Inspection | 5/20/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/20/2004 at 12:02:23 PM. Contact: ###-####. Dry sidewall heads not installed 5/21/2004 9:01:17 AM
|
BLD04-00151
| FIRE-Final Inspection | 5/20/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | A | FAIL |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Main exit will be keyed but other store front doors must be openable from the inside without special knowledge, etc. 5/21/2004 3:48:53 PM
|
FIR03-00252
| INSP-Final Inspection | 5/21/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | P | PASS |
|
|
Reschedule Ansul system final inspection. Problems have been corrected.; Phone #: ###-#### Internet Inspection Request from: Michael Heath
|
FIR04-00271
| INSP-Sprinkler Rough-in/Hydro | 5/21/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 5/21/2004 at 9:54:38 AM. Contact: ###-####. Okay to cover hard lids only; many changes made to piping; will require as-builts 5/21/2004 2:32:33 PM
|
BLD04-00070
| FIRE-Final Inspection | 5/21/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | P | PASS |
|
|
The extinguishing system was tied to the alarm system using the previous tenant connection 5/21/2004 10:10:24 AM
|
FIR04-00101
| INSP-Final Inspection | 5/21/2004 | 5/21/2004 | 5/21/2004 12:00:00 AM | P | FAIL |
|
|
Duct detectors aren't connected to HVAC units for shutdown 5/21/2004 3:47:56 PM
|