Inspections for the day of: Monday, May 21, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02465 FIRE-Final Inspection5/21/20075/21/20075/22/2007 8:28:51 AMPPASS
Final fire life safety inspection passed.
FIR07-00269 INSP-Alarm Testing5/18/20075/21/20075/21/2007 3:58:48 PMAPART
Fire alarm work tested satisfactory for the NE quad 1st floor as indicated on approved plans, noted the SD at the stairway exit is not yet programed for stairway pressure fans at this time.
BLD07-00352 FIRE-Final Inspection5/17/20075/21/20075/21/2007 3:54:45 PMAPART
Fire life safety is acceptable for the NE portion of the 1st floor remodel area.
FIR06-00800 INSP-Sprinkler Rough-in/Hydro5/21/20075/21/20075/21/2007 3:20:18 PMPPART
OH hydro for the dry system and the retest of the 3rd and 6th floor wet systems tests passed inspection.
FIR06-00800 INSP-Sprinkler Rough-in/Hydro5/21/20075/21/20075/21/2007 3:17:15 PMPFAIL
The second same day visit for fire pump testing is not ready for inspection due to leakage at the pump gasket and packing (allowed 25 minutes for contractor to make the necessary repairs which could not be completed while on site), incorrect pump motor rotation, jockey pump rotation not yet verified, concentric and eccentric reducers are installed at the incorrect locations, all sensing line piping shall be non-corrosive, it shall be the contractors responsibility to pre-test the system and it's components prior to scheduling acceptance testing per requirements of NFPA 20.
BLD06-02785 FIRE-Final Inspection5/21/20075/21/20075/21/2007 1:57:31 PMPPASS
Shell life safety passed.
FIR06-00800 INSP-Sprinkler Rough-in5/17/20075/21/20075/21/2007 1:39:18 PMAFAIL
We are having a pump start up at 8:00am.
This is to schedule the start up so you can
be there to witness. Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus...........................Contractor replacing a leaking gasket at the pump, noted installation not ready for inspection at the time of requested site visit.
FIR07-00034 INSP-Sprinkler Rough-in/Hydro5/18/20075/21/20075/21/2007 1:30:33 PMAPART
1st floor overhead hydrostatic test passed.
FIR06-00887 FIR-Aging Inspection5/21/20075/21/20075/21/2007 12:43:56 PM DONE
Work in progress.
FIR07-00131 INSP-Final Inspection5/18/20075/21/20075/21/2007 11:58:27 AMAPASS
Fire sprinkler permit work is approved for final, noted signage at the backflow to be installed as discussed and verified at BLD final.
FIR06-00645 INSP-Final Inspection5/18/20075/21/20075/21/2007 11:32:07 AMADEFR
Inspection to be rescheduled.
FIR07-00342 INSP-Sprinkler Rough-in5/18/20075/21/20075/21/2007 11:24:05 AMAFAIL
One room exceeds ordinary hazard group 2 spacing, ceilings are not completed in two rooms, all remaing drop ceiling areas are okay for cover, noted on plans.
BLD06-02665 FIRE-Final Inspection5/18/20075/21/20075/21/2007 10:49:08 AMAPASS
Required corrections have been made, fire life safety inspection passed.
FIR06-01002 INSP-Final Inspection5/21/20075/21/20075/21/2007 10:47:11 AMPPASS
Corrections verified, fire sprinkler permit finaled.