Inspections for the day of: Wednesday, May 21, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00997 INSP-Sprinkler Rough-in5/20/20085/21/20085/22/2008 1:22:12 PMAPART
System modifications per plan resubmittals completed okay, will need a hydrostatic test for the new heads and piping, noted missing ball drip at the FDC, also discussed items needed for final including forward flow test, alarm interconnections, etc.
FIR08-00124 INSP-Final Inspection5/20/20085/21/20085/21/2008 4:59:21 PMANR
rod Phone #: ###-####
FIR08-00124 INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008 4:59:00 PMAPART
Hydrostatic test for the east office area remodel and addition passed.
FIR08-00087 INSP-Final Inspection5/20/20085/21/20085/21/2008 4:57:50 PMPPASS
Corrections are complete, remainder of fire alarm testing passed inspection, map at the panel to be provided as discussed and verified at tomorrow's site visit, permit finaled.
FIR08-00160 INSP-Final Inspection5/21/20085/21/20085/21/2008 2:58:34 PMPNR
matt Phone #: ###-####
BLD07-03070 FIRE-Final Inspection5/21/20085/21/20085/21/2008 2:58:10 PMPNR
matt - fire life safety Phone #: ###-####
FIR08-00348 INSP-Sprinkler Rough-in5/20/20085/21/20085/21/2008 1:44:21 PMAPART
Overhead fire sprinkler modifications are okay for ceiling cover at the remodel area.
FIR07-00952 INSP-Final Inspection5/20/20085/21/20085/21/2008 1:30:20 PMAPASS
Fire alarm and elevator recall testing completed. KR
BLD07-02934 FIRE-Final Inspection5/20/20085/21/20085/21/2008 1:26:58 PMAFAIL
Fire extinguisher mounted to high see fire plan review notes item#3 for correct intalllation instructions. Missing suite # on door.
FIR06-00615 INSP-Final Inspection5/21/20085/21/20085/21/2008 11:14:23 AMPPASS
Fire sprinkler permit finaled.
FIR07-00905 INSP-Sprinkler Rough-in/Hydro5/21/20085/21/20085/21/2008 11:13:52 AMPCANC
Duplicate inspection request already completed.
FIR08-00257 INSP-Final Inspection5/20/20085/21/20085/21/2008 11:11:52 AMAPASS
Hood suppression system functioned properly under test conditions, permit finaled per KR.
FIR06-00615 INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008 11:06:00 AMAPASS
Resubmittals verified, permit okayed for final.
FIR08-00110 FIR-Aging Inspection5/21/20085/21/20085/21/2008 11:02:38 AM DONE
Under construction, work in progress.
FIR07-00905 INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008 11:00:46 AMAPART
Additional gate valve, new stub-in and ductile riser are approved for cover, need to plug the open cap at the riser and provide method for seismic clearance where the piping will pass through the floor slab, hydro and flushing not yet completed for this portion of work.
FIR08-00313 INSP-Alarm Testing5/20/20085/21/20085/21/2008 10:53:25 AMAFAIL
Voice evacuation communication is not sufficiently intelligible to be clearly understood-NFPA 72 2007 7.4.1.4, noted one non-required SD at the computer room has been installed per tenant request.