FIR07-00997
| INSP-Sprinkler Rough-in | 5/20/2008 | 5/21/2008 | 5/22/2008 1:22:12 PM | A | PART |
|
|
System modifications per plan resubmittals completed okay, will need a hydrostatic test for the new heads and piping, noted missing ball drip at the FDC, also discussed items needed for final including forward flow test, alarm interconnections, etc.
|
FIR08-00124
| INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 4:59:21 PM | A | NR |
|
|
rod Phone #: ###-####
|
FIR08-00124
| INSP-Sprinkler Rough-in/Hydro | 5/20/2008 | 5/21/2008 | 5/21/2008 4:59:00 PM | A | PART |
|
|
Hydrostatic test for the east office area remodel and addition passed.
|
FIR08-00087
| INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 4:57:50 PM | P | PASS |
|
|
Corrections are complete, remainder of fire alarm testing passed inspection, map at the panel to be provided as discussed and verified at tomorrow's site visit, permit finaled.
|
FIR08-00160
| INSP-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 2:58:34 PM | P | NR |
|
|
matt Phone #: ###-####
|
BLD07-03070
| FIRE-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 2:58:10 PM | P | NR |
|
|
matt - fire life safety Phone #: ###-####
|
FIR08-00348
| INSP-Sprinkler Rough-in | 5/20/2008 | 5/21/2008 | 5/21/2008 1:44:21 PM | A | PART |
|
|
Overhead fire sprinkler modifications are okay for ceiling cover at the remodel area.
|
FIR07-00952
| INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 1:30:20 PM | A | PASS |
|
|
Fire alarm and elevator recall testing completed. KR
|
BLD07-02934
| FIRE-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 1:26:58 PM | A | FAIL |
|
|
Fire extinguisher mounted to high see fire plan review notes item#3 for correct intalllation instructions. Missing suite # on door.
|
FIR06-00615
| INSP-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 11:14:23 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00905
| INSP-Sprinkler Rough-in/Hydro | 5/21/2008 | 5/21/2008 | 5/21/2008 11:13:52 AM | P | CANC |
|
|
Duplicate inspection request already completed.
|
FIR08-00257
| INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 11:11:52 AM | A | PASS |
|
|
Hood suppression system functioned properly under test conditions, permit finaled per KR.
|
FIR06-00615
| INSP-Sprinkler Rough-in/Hydro | 5/20/2008 | 5/21/2008 | 5/21/2008 11:06:00 AM | A | PASS |
|
|
Resubmittals verified, permit okayed for final.
|
FIR08-00110
| FIR-Aging Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 11:02:38 AM | | DONE |
|
|
Under construction, work in progress.
|
FIR07-00905
| INSP-Sprinkler Rough-in/Hydro | 5/20/2008 | 5/21/2008 | 5/21/2008 11:00:46 AM | A | PART |
|
|
Additional gate valve, new stub-in and ductile riser are approved for cover, need to plug the open cap at the riser and provide method for seismic clearance where the piping will pass through the floor slab, hydro and flushing not yet completed for this portion of work.
|
FIR08-00313
| INSP-Alarm Testing | 5/20/2008 | 5/21/2008 | 5/21/2008 10:53:25 AM | A | FAIL |
|
|
Voice evacuation communication is not sufficiently intelligible to be clearly understood-NFPA 72 2007 7.4.1.4, noted one non-required SD at the computer room has been installed per tenant request.
|