Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00204 INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008 4:33:18 PMAPASS
Sprinkler rough-in passed.
FIR08-00076 INSP-Final Inspection5/20/20085/21/20085/21/2008 4:08:39 PMAFAIL
The sprinkler interconnections were tested today. The tamper switches had to be adjusted so they would activate correctly. The riser waterflow switches and tamper switches need to be relabeled so that they matched the sprinkler contractors designations as sprinkler riser 1 and sprinkler riser 2. The horn in the electrical room was not sounding in a temporal pattern. After all of that was fixed I spent the remaining time testing all of the manual pull stations.
BLD07-00143 FIRE-Hydro test above ground5/20/20085/21/20085/21/2008 4:05:15 PMACANC
Wrong inspection type called in.
BLD07-00143 FIRE-Alarm Testing5/20/20085/21/20085/21/2008 4:04:12 PMADONE
See the related fire alarm permit for notes
FIR07-00579 INSP-Final Inspection5/21/20085/21/20085/21/2008 4:02:57 PMPPASS
Permit finaled
BLD08-00193 FIRE-Final Inspection5/21/20085/21/20085/21/2008 1:09:47 PMPFAIL
I left two messages and received no responce. There was no access to the restrooms.
BLD07-01639 FIRE-Conference5/20/20085/21/20085/21/2008 1:06:43 PMPPASS
Life safety passed
BLD07-01110 FIRE-Final Inspection5/21/20085/21/20085/21/2008 1:06:20 PMPPASS
Life safety passed
BLD07-02099 FIRE-Final Inspection5/20/20085/21/20085/21/2008 1:04:42 PMAFAIL
Remove the thumbturn from the main exit lock and provide an inspection tag for the fire extinguisher.