FIR08-00204
| INSP-Sprinkler Rough-in/Hydro | 5/20/2008 | 5/21/2008 | 5/21/2008 4:33:18 PM | A | PASS |
|
|
Sprinkler rough-in passed.
|
FIR08-00076
| INSP-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 4:08:39 PM | A | FAIL |
|
|
The sprinkler interconnections were tested today. The tamper switches had to be adjusted so they would activate correctly. The riser waterflow switches and tamper switches need to be relabeled so that they matched the sprinkler contractors designations as sprinkler riser 1 and sprinkler riser 2. The horn in the electrical room was not sounding in a temporal pattern. After all of that was fixed I spent the remaining time testing all of the manual pull stations.
|
BLD07-00143
| FIRE-Hydro test above ground | 5/20/2008 | 5/21/2008 | 5/21/2008 4:05:15 PM | A | CANC |
|
|
Wrong inspection type called in.
|
BLD07-00143
| FIRE-Alarm Testing | 5/20/2008 | 5/21/2008 | 5/21/2008 4:04:12 PM | A | DONE |
|
|
See the related fire alarm permit for notes
|
FIR07-00579
| INSP-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 4:02:57 PM | P | PASS |
|
|
Permit finaled
|
BLD08-00193
| FIRE-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 1:09:47 PM | P | FAIL |
|
|
I left two messages and received no responce. There was no access to the restrooms.
|
BLD07-01639
| FIRE-Conference | 5/20/2008 | 5/21/2008 | 5/21/2008 1:06:43 PM | P | PASS |
|
|
Life safety passed
|
BLD07-01110
| FIRE-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 1:06:20 PM | P | PASS |
|
|
Life safety passed
|
BLD07-02099
| FIRE-Final Inspection | 5/20/2008 | 5/21/2008 | 5/21/2008 1:04:42 PM | A | FAIL |
|
|
Remove the thumbturn from the main exit lock and provide an inspection tag for the fire extinguisher.
|