Inspections for the day of: Thursday, May 21, 2009.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00295 INSP-Alarm Testing5/19/20095/21/20095/21/2009 4:25:24 PMPFAIL
Provide visual notification in the short north corridor as requested on the city approved plans. Resubmittals not required. The end of line voltage drops are acceptable.
BLD08-01210 FIRE-Final Inspection5/21/20095/21/20095/21/2009 3:41:15 PMPFAIL
Provide a letter from plan review stating that the exit sign on the roof can be deleted. Provide and test all items pertaining to the Area of Refuge. Provide testing of the elevator and fire alarm interconnections. The building address does not match the address the central station give to the boise fire dept. This will have to have approval.
FIR08-00679 INSP-Final Inspection5/21/20095/21/20095/21/2009 3:35:18 PMPFAIL
All items have been tested except the elevator recall/voltage monitoring interconnections.
FIR08-00675 INSP-Final Inspection5/21/20095/21/20095/21/2009 3:32:13 PMPPASS
Permit finaled
BLD08-01944 FIRE-Final Inspection5/21/20095/21/20095/21/2009 2:51:11 PMPPASS
LIfe safety passed.
FIR06-00362 INSP-Conference5/20/20095/21/20095/21/2009 2:50:17 PMADONE
I spoke to Adam and told him that an inspector would need to witness that the signals had been corrected and then the permit could be finaled.
FIR08-00755 INSP-Final Inspection5/21/20095/21/20095/21/2009 2:40:42 PMPPASS
Permit finaled
FIR09-00326 INSP-Sprinkler Rough-in5/20/20095/21/20095/21/2009 2:40:18 PMAPASS
The 6" underground piping from the point of connection up to where the PIV will be installed is ok to cover.
FIR09-00095 FIR-Aging Inspection5/21/20095/21/20095/21/2009 1:14:15 PM NR
Work is in progress
BLD07-01834 FIRE-Conference5/19/20095/21/20095/21/2009 11:39:53 AMADONE
I met with John/Petra and Rod/Grinnell about what I would be looking for with the modified suppression system at the existing kitchen hood.
BLD09-00727 FIRE-Final Inspection5/20/20095/21/20095/21/2009 10:41:19 AMAFAIL
Remove the dead bolt from the rear exit door, provide sprinkler protection for the house display and have the floor pan shown on the approved plans or remove all together or remove the ceiling/deck and have the floor plan shon on the approved plans. Also provide verification of the annual inspection for the existing fire sprinkler system.
BLD09-00754 FIRE-Final Inspection5/20/20095/21/20095/21/2009 9:51:38 AMAPART
A temporary occupancy was given until an additional exit sign/emergency light is provided at the main exit, the rear exit sign and emergency lights are repaired, the rear dead bolt is removed, a fire extinguisher is provided and the electrical outlets are covered.
FIR09-00103 INSP-Final Inspection5/20/20095/21/20095/21/2009 8:49:44 AMAFAIL
All of the devices tested ok but as per the approved drawings if no notification devices have been provided in the new lobby area they shall be. No devices have been provided in this new lobby. Also there are sync issues and was discussed with Mark.