Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02310 Final5/21/20105/21/20105/24/2010 11:06:33 AMPPASS
Inspection requested from web by: Mark Sessions Phone #: ###-#### ok card signed
ELE10-01128 Rough-In Permanent Service5/21/20105/21/20105/24/2010 11:05:50 AMPPASS
Daniel Phone #: ###-#### r/i p/s u/g new ok
ELE10-00237 Final5/21/20105/21/20105/24/2010 9:55:00 AMPPASS
cal Phone #: ###-####
ELE10-00301 Final5/21/20105/21/20105/24/2010 9:54:44 AMPPASS
cal Phone #: ###-####
ELE10-00300 Final5/21/20105/21/20105/24/2010 9:54:28 AMPPASS
cal Phone #: ###-####
ELE10-00616 Final5/21/20105/21/20105/24/2010 9:54:13 AMPPASS
cal Phone #: ###-####
ELE10-00549 Final5/21/20105/21/20105/24/2010 9:53:55 AMPPASS
cal Phone #: ###-####
ELE10-00694 Final5/21/20105/21/20105/24/2010 7:52:27 AMPPASS
garage code is 31629, thx. Inspection requested from web by: Stephen Kren Phone #: ###-####
ELE08-01742 ELE-Aging Inspection5/21/20105/21/20105/21/2010 3:54:31 PM CANC
ELE08-01742 DOC - Permit Expired5/21/20105/21/20105/21/2010 3:54:19 PMPPASS
ELE07-03623 ELE-Aging Inspection5/21/20105/21/20105/21/2010 3:53:01 PM CANC
ELE07-03623 DOC - Permit Expired5/21/20105/21/20105/21/2010 3:52:50 PMPPASS
no activity
ELE10-00873 Final5/19/20105/21/20105/21/2010 3:50:41 PMAFAIL
Mark please call before going out. If possible 8am would be great. Phone #: ###-#### talked with owner electrical contr still needs permit for the work he did , he cannot do work on homeowner permit
ELE10-01116 Electrical Rough-In5/20/20105/21/20105/21/2010 3:47:47 PMAPASS
Heath ###-#### ok
ELE10-00883 Electrical Rough-In5/20/20105/21/20105/21/2010 3:47:29 PMAPASS
potting compound inspection Inspection requested from web by: Kevin Koomler Phone #: ###-#### ok
ELE10-01113 Permanent Service5/21/20105/21/20105/21/2010 3:47:09 PMPPASS
Inspection requested from web by: Emmet Bushman Phone #: ###-#### p/s u/g new ok
ELE10-01113 Final5/21/20105/21/20105/21/2010 3:46:48 PMPPASS
Inspection requested from web by: Emmet Bushman Phone #: ###-####
ELE10-00940 Electrical Rough-In5/20/20105/21/20105/21/2010 3:46:17 PMAFAIL
Contact: Brian Gee. Rough-in inspection of Laundry Facililty only. Inspection requested from web by: Shelli Daylong Phone #: ###-#### corr called 300.4(D) 11/4" for cables parallel
ELE10-00889 Electrical Rough-In5/20/20105/21/20105/21/2010 3:38:57 PMAPASS
ceiling only Inspection requested from web by: Jim Williams Phone #: ###-####
ELE10-01111 Rough-In Permanent Service5/20/20105/21/20105/21/2010 12:57:04 PMAFAIL
Daryl Kubik ###-#### corr. 300.4(A)(1) & (D) nail plates for holes , and 11/4" for cables parallel to framing members 210.52(B) remove vacuum outlet from small appliance branch circuit, 334.23 protect all cables within 6ft of both attic accesses, 314.17 & 800.24 needs connectors for all cables at low voltage cabinet upstairs closet
ELE10-01084 Electrical Rough-In5/18/20105/21/20105/21/2010 11:51:05 AMAPASS
Inspection requested from web by: Emmet Bushman Phone #: ###-#### ok
ELE10-00794 Electrical Rough-In5/20/20105/21/20105/21/2010 11:50:34 AMAPASS
Master bedroom and bathroom remodel of lights and outlets. Homeowner will be there Inspection requested from web by: Joe Thomas Phone #: ###-#### ok
ELE10-01122 Final5/21/20105/21/20105/21/2010 11:09:38 AMPCANC
We wired up 220 blower in attic Inspection requested from web by: Barbara Szurgot Phone #: ###-#### Inspection cancelled from web by: Barbara Szurgot
ELE10-01114 Temporary Service5/20/20105/21/20105/21/2010 10:10:07 AMAFAIL
greg - if questions about the rod call greg Phone #: ###-#### called needs WR recpt, also grd rod shall be install as NEC statesall 8ft driven flush with grade
ELE10-01099 Electrical Rough-In5/20/20105/21/20105/21/2010 9:58:48 AMAPART
Neil Phone #: ###-#### new kitchen only, told owner and contr all prior electrical work done without permit and inspection regaurdless of who did the work shall be uncovered and inspected and all violations fixed to meet 2008 NEC, no exception
ELE10-01093 Electrical Rough-In5/20/20105/21/20105/21/2010 8:30:48 AMAPASS
new basement area and new upstairs area
ELE10-01119 Conference5/20/20105/21/20105/21/2010 8:01:39 AMADONE
Rick Phone #: ###-#### had phone conference with owner 05-20-10
ELE09-02289 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:18:48 AM CANC
ELE07-03709 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:18:35 AM CANC
ELE07-03709 DOC - Permit Expired5/21/20105/21/20105/21/2010 7:18:29 AMAPASS
ELE07-04115 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:17:47 AM CANC
ELE07-04115 DOC - Permit Expired5/21/20105/21/20105/21/2010 7:17:40 AMAPASS
ELE09-02346 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:17:00 AM CANC
ELE07-04228 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:16:44 AM CANC
ELE07-04228 DOC - Permit Expired5/21/20105/21/20105/21/2010 7:16:37 AMAPASS
ELE07-03985 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:16:10 AM CANC
ELE07-03985 DOC - Permit Expired5/21/20105/21/20105/21/2010 7:16:02 AMAPASS
ELE09-02254 ELE-Aging Inspection5/21/20105/21/20105/21/2010 7:15:21 AM CANC
ELE10-00694 Final5/20/20105/21/20105/21/2010 7:07:59 AMACANC
Garage code is; 31629, thx. Inspection requested from web by: Stephen Kren Inspection cancelled from web by: Stephen Kren