Inspections for the day of: Wednesday, May 21, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00913 ELE-Aging Inspection5/21/20145/21/20145/27/2014 10:23:09 AM DONE
left message
ELE12-02301 ELE-Aging Inspection5/21/20145/21/20145/27/2014 10:19:37 AM DONE
called but no way to leave message
ELE14-01301 Temporary Service5/21/20145/21/20145/21/2014 3:18:36 PMPPASS
ELE-INSPECTOR t/s u/g n ok
ELE14-00640 Final5/20/20145/21/20145/21/2014 3:05:13 PMPFAIL
ELE-INSPECTOR a/c cond. unit says max. breaker 25amp. lockoff on breaker for furnace needed. flash ring needed on kitchen pendant switch in tile backsplash.
ELE14-01071 Electrical Rough-In5/20/20145/21/20145/21/2014 2:30:03 PMPPASS
ELE-INSPECTOR phase 2, 2nd floor rough in walls n.east offices ok to cover
ELE14-00504 Electrical Rough-In5/15/20145/21/20145/21/2014 2:12:30 PMPPASS
Ceiling inspection. Jake is the contact his cell is ###-####. Phone #: ###-#### >> Inspection requested via web by Mike Basye rough in ceilings ok to cover
MIS14-00112 ELE-Conference5/21/20145/21/20145/21/2014 12:28:43 PMPDONE
meet Gorden Goldsmith with Boise fire dept. to look at electrical overhead wiring needing to be de energized because of garage fire. owner of residence says he will hire electrical contractor to separate electrical from house within 24 hrs of correction notice
ELE14-01124 Electrical Rough-In5/21/20145/21/20145/21/2014 12:12:49 PMAFAIL
ELE-INSPECTOR 334.30 secure nm cable min. every 4 1/2 feet above sub-panel in hall. 300.4D 11/4 min to nm cable from edge of framing. under subpanel and 1/0ser in kitchen. Exhaust fan not installed and waterbond ground needs to be connected.
ELE14-00910 Final5/20/20145/21/20145/21/2014 11:39:51 AMAPASS
ELE-INSPECTOR final ok
ELE14-00992 Final5/21/20145/21/20145/21/2014 11:26:53 AMAFAIL
ELE-INSPECTOR box extensions 314.20 in breakroom backsplash
ELE14-00817 Final5/20/20145/21/20145/21/2014 10:58:32 AMACANC
ELE-INSPECTOR needed rough in insp.
ELE14-00817 Electrical Rough-In5/21/20145/21/20145/21/2014 10:58:07 AMPPASS
ELE-INSPECTOR rough in ok to cover house and garage
GCE14-00075 GCE-Final5/21/20145/21/20145/21/2014 10:05:03 AMPPASS
Joel Smith ###-#### call for access; installer will meet inspector final ok
ELE13-02849 Electrical Rough-In5/19/20145/21/20145/21/2014 9:27:12 AMACANC
Contact is Alan Krishnek ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell cancelled as per alan
ELE14-00981 Final5/20/20145/21/20145/21/2014 9:05:26 AMAPASS
ELE-INSPECTOR final ok