FIR15-00327
| INSP-Final Inspection | 5/20/2015 | 5/21/2015 | 5/22/2015 11:23:13 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00209
| INSP-Final Inspection | 5/20/2015 | 5/21/2015 | 5/22/2015 11:17:11 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00307
| INSP-Sprinkler Rough-in/Hydro | 5/20/2015 | 5/21/2015 | 5/22/2015 10:09:21 AM | P | CANC |
|
|
To be rescheduled for next week
|
FIR15-00254
| INSP-Final Inspection | 5/20/2015 | 5/21/2015 | 5/22/2015 9:16:55 AM | P | PASS |
|
|
Permit finaled
|
FIR14-00799
| INSP-Sprinkler Rough-in | 5/20/2015 | 5/21/2015 | 5/21/2015 3:31:49 PM | A | PASS |
|
|
Second floor rough-in passed. As-builts will be required for pipe routing changes and head additions.
|
BLD14-00544
| FIRE-Final Inspection | 5/20/2015 | 5/21/2015 | 5/21/2015 3:20:45 PM | A | PART |
|
|
The life safety in the "M" occupancy area of this project is passed. No distilling or "manufacturing" allowed at this time. I went over the life safety requirements as noted on the Fire Dept Plan Review Comments.
|
BLD14-00764
| FIRE-Final Inspection | 5/20/2015 | 5/21/2015 | 5/21/2015 1:41:52 PM | P | PASS |
|
|
Life safety passed
|
FIR15-00076
| INSP-Sprinkler Rough-in/Hydro | 5/20/2015 | 5/21/2015 | 5/21/2015 10:36:10 AM | A | PASS |
|
|
Piping rough-in passed. Piping can be covered.
|
FIR15-00075
| INSP-Final Inspection | 5/20/2015 | 5/21/2015 | 5/21/2015 10:32:42 AM | A | PASS |
|
|
Permit finaled
|
GCB14-00099
| FIRE-Conference | 5/20/2015 | 5/21/2015 | 5/21/2015 10:18:16 AM | A | DONE |
|
|
Gary, myself, the electrician and the fire sprinkler contractor discussed obstructions to the fire sprinkler pendants and the required separation distances.
|
FIR15-00311
| INSP-Sprinkler Rough-in | 5/20/2015 | 5/21/2015 | 5/21/2015 9:42:49 AM | A | PASS |
|
|
underground supply piping is ok to cover
|
FIR15-00064
| INSP-Alarm Testing | 5/20/2015 | 5/21/2015 | 5/21/2015 9:18:27 AM | A | DONE |
|
|
See the city approved plans for locations and devices tested which included the elevator recall. Elevator fire doors need to be adjusted/repaired, PIV needs adjusted and the outside alarm bell did not function.
|
FIR14-00242
| INSP-Final Inspection | 5/19/2015 | 5/21/2015 | 5/21/2015 6:43:34 AM | A | CANC |
|
|
Please give me a call to schedule a time. -Jason Gordon ###-#### Phone #: ###-#### >> Inspection requested via web by Neal Timmerman Inspection cancelled from web by: Neal Timmerman
|
BLD14-03713
| FIRE-Final Inspection | 5/19/2015 | 5/21/2015 | 5/21/2015 12:00:00 AM | A | CANC |
|
|
Randy-call prior to meet Phone #: ###-####
|