FIR18-00510
| INSP-Sprinkler Rough-in | 5/21/2019 | 5/21/2019 | 5/21/2019 4:36:11 PM | P | PART |
|
|
2nd floor apartments approved for cover, level 5 corridor drop down ceilings, north of the fire doors approved for cover
2nd floor apartments and 4th floor corridor Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-00281
| FIRE-Final Inspection | 5/21/2019 | 5/21/2019 | 5/21/2019 2:35:48 PM | P | PART |
|
|
Fire sprinkler inspection complete for scope of work, fire alarm inspection has been completed but plan is back into reviewed status due to plan mod, fire extinguishers are placed with current inspection tags. 30 day TCO authorized for life fire safety contingent on fire alarm plans being approved and finaled.
Phone #: 2083188954 >> Inspection requested via mobile web by Jim Douglas
|
FIR19-00181
| INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 2:33:57 PM | A | PART |
|
|
Fina fire alarm inspection for scope of work complete, awaiting plan mod approval for final sign off.
(plan mod in process)
Ron ###-####
|
BLD18-04006
| FIRE-Final Inspection | 5/21/2019 | 5/21/2019 | 5/21/2019 1:26:03 PM | P | PASS |
|
|
Previously noted items have been corrected, fire exitnguisher was mounted in discussed location at time of inspection. Slide bolts were removed at time of inspection, final life fire safety inspection for area of work complete.
Alician Phone #: ###-####
|
BLD18-04174
| FIRE-Final Inspection | 5/21/2019 | 5/21/2019 | 5/21/2019 1:14:06 PM | P | CANC |
|
|
No fire life safety signature required for permit according to permit details, this request is cancelled.
Toby Phone #: ###-####
|
BLD18-04173
| FIRE-Final Inspection | 5/21/2019 | 5/21/2019 | 5/21/2019 1:13:46 PM | P | CANC |
|
|
No fire life safety signature required for permit according to permit details, this request is cancelled.
Toby Phone #: ###-####
|
BLD17-04465
| FIRE-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 1:10:17 PM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire exitnguishers are placed with current inspection tags, knox box is located by fire sprinkler riser room. Final life fire safety inspection complete.
Wes Phone #: ###-####
|
FIR19-00091
| INSP-Supply line flush | 5/21/2019 | 5/21/2019 | 5/21/2019 12:49:34 PM | A | DONE |
|
|
Underground main line flush complete.
Troy Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD18-03875
| FIRE-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 12:19:37 PM | A | FAIL |
|
|
Fire sprinkler inspection failed due to a painted head and texture mud all the way up to the base of the sprinkler head. An FIR permit is required for fire alarm work, currently there is a wall mounted device mounted on the ceiling, was informed by the GC that the devices were lowered from their original location, any modifications to the fire alarm system requires a permit, including lowering devices from the original location.
Marty Phone #: ###-####
|
FIR19-00287
| INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 12:17:33 PM | A | FAIL |
|
|
Fire sprinkler head in changing room has paint on the seat, head will need to be replaced. Texture mud needs to be cut around the other 2 heads in changing room, heads to not have escutcheons installed due to drywall mud issue.
Adam Chitwood To coinside with the fire life safety final. Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
BLD18-04124
| FIRE-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 11:38:50 AM | A | FAIL |
|
|
FIR permit for fire alarms still in issued status, reference FIR19-00089 for fire alarm notes. FIR permit for fire alarm system needs to be finaled before life fire safety can be completed.
Antonio Phone #: ###-####
|
FIR19-00111
| INSP-Sprinkler Rough-in/Hydro | 5/20/2019 | 5/21/2019 | 5/21/2019 11:21:17 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Leroy Anderson ###-#### 30 Min Prior to Hydro Insp start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00795
| INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/21/2019 8:36:59 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
|
FIR19-00287
| INSP-Final Inspection | 5/20/2019 | 5/21/2019 | 5/20/2019 8:52:01 AM | P | CANC |
|
|
Adam Chitwood To coinside with the fire life safety final Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist Inspection cancelled from web by: Brodie Stenquist
|