Inspections for the day of: Monday, May 22, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01523 Electrical Rough-In5/22/20065/22/20065/22/2006 3:52:02 PMPNH
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
notice posted called
ELE06-01839 Permanent Service5/22/20065/22/20065/22/2006 3:15:09 PMPPASS
MIKE ###-#### p/s damaged from wind
p/s o/h rec. ok
ELE06-01839 Final5/22/20065/22/20065/22/2006 3:14:15 PMPPASS
MIKE ###-####
ELE06-01820 Permanent Service5/19/20065/22/20065/22/2006 2:40:58 PMPPASS
mitch ###-####/ call 1/2 hour prior to inspection/service on house only/blb
p/s o/h rec. ok
ELE06-01592 Permanent Service5/22/20065/22/20065/22/2006 2:04:43 PMPNR
JACK, WE NEED POWER, THANKS BILL; Phone #: ###-#### Internet Inspection Request from: Bob Glenn needs to remove conduit for GEC from below panel class 1 div 2 area called
ELE06-01836 Final5/22/20065/22/20065/22/2006 1:23:49 PMPNH
FINAL INSPECTION FOR A SPA PLEASE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall notice posted called also r/i inspection not a final
ELE06-01791 Temporary Service5/22/20065/22/20065/22/2006 1:22:31 PMPFAIL
Internet Inspection Request from: Latisha Peltier corr. called shall terminate GEC too electrode
ELE06-01831 Rough-In Permanent Service5/22/20065/22/20065/22/2006 12:58:39 PMPPASS
rick ###-#### move phone from below p/s,
r/i p/s u/g new ok
ELE06-01761 Permanent Service5/22/20065/22/20065/22/2006 12:06:48 PMPPASS
rick ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s u/g new ok
ELE06-00391 Rough-In Permanent Service5/19/20065/22/20065/22/2006 10:24:07 AMAFAIL
debbie; Phone #: ###-#### owner ###-#### - jan please call her 1/2 hr Internet Inspection Request from: Letitia corr. called 250.119 shall not use green foe neutral, 344.46 bushings for all rigid, 312.5 conn. for GEC note partial corr. only job not complete
ELE06-00884 Electrical Rough-In5/20/20065/22/20065/22/2006 9:50:54 AMAPART
post light trench inspect Internet Inspection Request from: Melyne Davis u/g ok protect at house
ELE06-01101 Electrical Rough-In5/20/20065/22/20065/22/2006 9:50:27 AMAPART
post light trench inspect Internet Inspection Request from: Melyne u/g ok protect at house
ELE06-00885 Electrical Rough-In5/20/20065/22/20065/22/2006 9:49:58 AMAFAIL
post light trench inspect Internet Inspection Request from: Melyne Davis corr. called protect uf where it passes under sidewalk 300.5 and at house
ELE06-01750 Electrical Rough-In5/20/20065/22/20065/22/2006 9:48:44 AMAPART
post light trench inspect Internet Inspection Request from: Melyne u/g ok protect uf at house
ELE06-01751 Electrical Rough-In5/20/20065/22/20065/22/2006 9:48:09 AMAPART
post light trench inspect Internet Inspection Request from: Melyne Davis u/g ok protect uf at house
ELE06-01791 Temporary Service5/19/20065/22/20065/22/2006 8:59:46 AMANR
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier no t/s at site
ELE06-01816 Final5/19/20065/22/20065/22/2006 8:33:53 AMANR
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called job not ready, also p/s not final
ELE06-01790 Electrical Rough-In5/20/20065/22/20065/20/2006 8:09:37 AMACANC
post light trench inspect Internet Inspection Request from: Melyne Davis Inspection cancelled from web by: Melyne Davis