BLD07-00111
| FIRE-Final Inspection | 5/22/2007 | 5/22/2007 | 5/22/2007 5:14:52 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR07-00195
| INSP-Alarm Testing | 5/22/2007 | 5/22/2007 | 5/22/2007 5:12:21 PM | P | PART |
|
|
Tested sprinkler monitoring, manual pull, panel smoke, panel troubles, batteries, AC power, and building notification. Elevator is not ready for inspection at this time, need list of signals as discussed.
|
FIR05-00270
| INSP-Final Inspection | 5/21/2007 | 5/22/2007 | 5/22/2007 5:08:57 PM | P | PASS |
|
|
Fire sprinkler permit passed final inspection.
|
FIR07-00430
| INSP-Sprinkler Rough-in | 5/22/2007 | 5/22/2007 | 5/22/2007 5:03:12 PM | P | NR |
|
|
Work is not yet completed for inspection.
|
BLD07-00436
| FIRE-Final Inspection | 5/22/2007 | 5/22/2007 | 5/22/2007 5:02:10 PM | P | PASS |
|
|
Fire life safety inspection passed, the fire extinguisher is to be attatched to the wall as discussed prior to BLD final.
|
FIR07-00365
| INSP-Final Inspection | 5/22/2007 | 5/22/2007 | 5/22/2007 1:34:24 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00800
| INSP-Sprinkler Rough-in | 5/21/2007 | 5/22/2007 | 5/22/2007 11:42:14 AM | A | PART |
|
|
Fire pump acceptance testing completed including manual and automatic starts/stops, flow testing, performance curve, pump and jockey controller testing, timed run, phase reversal, and roof top flow test. Mfg. rep to fax field and shop curve data as discussed. Contractor to change out black steel pipe in the sensing lines for non-corrosive as required, also need to separately pipe the relief valve drain to its own termination point. Noted ball vavles for isolation of the jockey pump have been used in place of the recommended gate or butterfly type, sensing line configuration slightly differs from NFPA 20 figures, noted two pluged outlets on the eccentric reducer.
|
FIR06-00800
| INSP-Sprinkler Rough-in | 5/21/2007 | 5/22/2007 | 5/21/2007 4:17:54 PM | A | CANC |
|
|
We are having a pump start up at 8:00am. This is to schedule the start up so you can be there to witness. Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|