FIR08-00317
| INSP-Sprinkler Rough-in/Hydro | 5/21/2008 | 5/22/2008 | 5/22/2008 5:18:43 PM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
FIR08-00362
| INSP-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 4:20:12 PM | P | PASS |
|
|
Full function test on kitchen fire supression system. kr
|
FIR08-00340
| INSP-Final Inspection | 5/22/2008 | 5/22/2008 | 5/22/2008 3:34:11 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00213
| INSP-Sprinkler Rough-in/Hydro | 5/21/2008 | 5/22/2008 | 5/22/2008 3:29:57 PM | P | PASS |
|
|
Underground hydro test passed
|
FIR07-00212
| INSP-Sprinkler Rough-in/Hydro | 5/21/2008 | 5/22/2008 | 5/22/2008 3:28:57 PM | P | PASS |
|
|
Underground hydro test passed
|
FIR08-00204
| INSP-Sprinkler Rough-in/Hydro | 5/21/2008 | 5/22/2008 | 5/22/2008 3:25:55 PM | A | CANC |
|
|
Tenting was not complete per the fitter. No inspection performed
|
FIR08-00166
| INSP-Final Inspection | 5/20/2008 | 5/22/2008 | 5/22/2008 3:02:44 PM | P | PASS |
|
|
Fire alarm testing complete. KR
|
BLD08-00280
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 1:16:19 PM | A | PASS |
|
|
Life safety passed
|
BLD08-00193
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 12:34:44 PM | A | CANC |
|
|
Could not get power to building to test mag locks.
|
FIR08-00076
| INSP-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 12:22:38 PM | A | FAIL |
|
|
Provide modifications to the attic area a/v's as discussed to meet code requirements. Need to test the duct smoke detectors and in-duct detectors in heat mode to verify shutdown. Many of the main level a/v's are not using temporal but are sounding with two pulses the same time as other are doing the temporal. The a/v in room 202 is overspaced. As-builts will be needed prior to sign off of this permit.
|
FIR08-00250
| INSP-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 11:58:57 AM | A | PASS |
|
|
permit finaled
|
BLD07-01943
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 11:57:52 AM | A | PASS |
|
|
life safety passed
|
BLD07-02935
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 11:30:57 AM | A | FAIL |
|
|
See the city approved notes for items circled in red ink that need addressed. Items include the correct annunciators for the duct smoke detectors, address installed, emergency lighting and exit signs tested....ect. Also a suppression system has been installed and I can find no attached FIR permit for this work. Per the general contractor the installer was General Fire. I contacted Scott in our office about double fees when this permit comes in. Basically not inspection was performed but a conference was held.
|
BLD08-00281
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 11:19:43 AM | A | PASS |
|
|
Life safety passed
|
BLD07-02099
| FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 10:12:15 AM | A | PASS |
|
|
Life safety passed
|
FIR08-00214
| INSP-Conference | 5/21/2008 | 5/22/2008 | 5/22/2008 7:40:08 AM | A | DONE |
|
|
The high area sprinkler piping can now be covered.
|