BLD14-00321
| FIRE-Final Inspection | 5/22/2014 | 5/22/2014 | 5/22/2014 3:27:55 PM | P | FAIL |
|
|
inspection was actually for a conference. Larry and I went over exit sign placement and occupant load sign requirements.
|
BLD13-03261
| FIRE-Final Inspection | 5/22/2014 | 5/22/2014 | 5/22/2014 3:04:45 PM | P | PASS |
|
|
Life safety passed
|
BLD13-02228
| FIRE-Final Inspection | 5/21/2014 | 5/22/2014 | 5/22/2014 2:57:41 PM | A | FAIL |
|
|
Provide final for the fire alarm permit. Provide final for the fire sprinkler permit. Remove the thumbturn on the main exit, provide indicator and sticker. Provide panic hardware on the doors indicated on the approved plans. Provide fire dept. access signage. Provide address. Provide signage on riser room door.
|
FIR14-00183
| INSP-Final Inspection | 5/22/2014 | 5/22/2014 | 5/22/2014 2:50:06 PM | P | PASS |
|
|
permit finaled
|
FIR13-00618
| INSP-Final Inspection | 5/21/2014 | 5/22/2014 | 5/22/2014 2:49:11 PM | P | FAIL |
|
|
Provide re-submittals as previously discussed. Forward flush passed and final rough-in inspection for the office area passed.
|
FIR13-00568
| INSP-Alarm Testing | 5/21/2014 | 5/22/2014 | 5/22/2014 2:47:02 PM | P | FAIL |
|
|
Delete phone line #1 as discussed (Tyco Security providing monitoring) and provide duct smoke detector for the 3,000cfm unit shown on the mechanical plans. Will need as-builts
|
BLD13-03560
| FIRE-Final Inspection | 5/22/2014 | 5/22/2014 | 5/22/2014 12:26:55 PM | P | PASS |
|
|
life safety passed
|
BLD14-00604
| FIRE-Final Inspection | 5/21/2014 | 5/22/2014 | 5/22/2014 11:22:57 AM | A | CANC |
|
|
Per scott and I's discussion a fire alarm contractor is going to verify modifications
|
FIR14-00297
| INSP-Sprinkler Rough-in | 5/21/2014 | 5/22/2014 | 5/22/2014 9:57:39 AM | A | PASS |
|
|
Underground piping is ok to cover.
|
FIR14-00298
| INSP-Sprinkler Rough-in | 5/21/2014 | 5/22/2014 | 5/22/2014 9:57:09 AM | A | PASS |
|
|
Underground piping is ok to cover.
|