MEC18-02163
| Rough-in | 5/22/2018 | 5/22/2018 | 5/22/2018 4:03:37 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Krista Boss - Fresh air to furnace is not allowed to be pulled from the roof, need to seal exhaust duct where it connects to the fan.
|
MEC17-01469
| Mec-Aging Inspection | 5/22/2018 | 5/22/2018 | 5/22/2018 3:07:16 PM | | DONE |
|
|
Expired
|
MEC17-01469
| DOC - Permit Expired | 5/22/2018 | 5/22/2018 | 5/22/2018 3:06:45 PM | P | PASS |
|
|
|
MEC18-02270
| Pressure Test | 5/22/2018 | 5/22/2018 | 5/22/2018 2:58:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - 20lb gas, 5lb flue
|
MEC18-02270
| Rough-in | 5/22/2018 | 5/22/2018 | 5/22/2018 2:58:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
MEC18-02063
| Final | 5/15/2018 | 5/22/2018 | 5/22/2018 1:27:18 PM | P | FAIL |
|
|
Customer would like afternoon. Please call when on your way. Kirsten - ###-#### Phone #: ###-#### Inspection requested via web by Jerry Crist - flue pressure test needs to be witnessed, Fuses for A/C are over sized, need to pull plumbing permit for water heater
|
MEC17-01976
| Final | 5/21/2018 | 5/22/2018 | 5/22/2018 10:52:33 AM | A | FAIL |
|
|
Whole building Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN - Missing fire damper in trash room, missing duct access doors for fire/smoke dampers in 4th floor mech room, need screws every 6" on retaining angles on dampers in 4th floor mechanical room, missing return and return transfers in office area, need to secure fans and hoods to curbs on roof, need completed generator commisioning report.
|