Inspections for the day of: Wednesday, May 22, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01963 ELE-Aging Inspection5/22/20195/22/20195/23/2019 4:27:41 PM FAIL
Final inspection required.
ELE19-01316 Electrical Rough-In5/22/20195/22/20195/22/2019 3:08:28 PMPPASS
Late afternoon if possible. Phone #: ###-#### Inspection requested via web by Kevin Burke
Called and attached to BLD18-03116.
Units 103, 104, 203, 204, 303, 304. 2nd 6 from south rough in ok cover.
ELE19-00734 Final5/22/20195/22/20195/22/2019 2:08:35 PMPFAIL
if no answer at above number call ###-#### Phone #: ###-#### Inspection requested via web by Robert Murray
314.16- Island receptacle box is an 8 cubic inch box with 11.25 cubic inch of conductor installed.
ELE19-00619 Final5/22/20195/22/20195/22/2019 2:05:58 PMPFAIL
if no answer at above number call ###-#### Phone #: ###-#### Inspection requested via web by Robert Murray
314.16- Island receptacle box is an 8 cubic inch box with 11.25 cubic inch of conductor installed.
314.25- All boxes shall have covers. Microwave not trimmed.
ELE19-01875 Rough-In Permanent Service5/21/20195/22/20195/22/2019 1:19:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Same Electric
p/s o/h rec ok
ELE19-01813 Rough-In Permanent Service5/22/20195/22/20195/22/2019 12:29:49 PMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Wires coiled in walls above fireplace and center wall to right of fireplace and level 2 attic boxes trimmed on rough in.
Rough in ok cover p/s u/g n ok
ELE18-04013 Final5/21/20195/22/20195/22/2019 11:28:20 AMAFAIL
Roof Top units ready for final. Jason is our contact at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Kelly Felin
408.4- Circuit directory shall be accurately labeled as to which unit supplied with unit marked with identification of circuit or individual unit.
440.4- Overcurrent protection shall not exceed value given on name plate.
ELE19-01647 Electrical Rough-In5/20/20195/22/20195/22/2019 10:36:34 AMAPASS
Call foreman, Brad Hallman, one hour prior to arrival to coordinate. Phone #: ###-#### Inspection requested via web by Rob Maes
Silfab is the solar panel of record and the brand installed. Listings confirmed rough in ok.
ELE19-01749 Electrical Rough-In5/21/20195/22/20195/22/2019 10:21:23 AMAFAIL
Malcolm Phone #: ###-####
210.11- Garage receptacle circuit shall have no other outlets. Garage lighting on with receptacles and 14 ga. wire installed as jumpers between lights and travellers in garage.
ELE19-01458 Permanent Service5/21/20195/22/20195/22/2019 9:47:11 AMAPASS
Phone #: ###-#### Inspection requested via web by jamie berg p/s o/h n ok
ELE19-01682 Final5/21/20195/22/20195/22/2019 9:32:18 AMAPASS
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER
Final ok
ELE19-01883 Permanent Service5/21/20195/22/20195/22/2019 9:11:53 AMAFAIL
Power off for over one year. Need inspection to turn power on. Please call Ryan for lock box code ###-#### Phone #: ###-#### Inspection requested via web by Ryan Schaffer 110.26(A)- Minimum work space shall be provided for meter base and both service disconnecting means of 30" wide and 36" deep. Remove evergreens to minimum required.
250.20- Services operating at 50 to 1000 volts shall be grounded. Unable to verify grounding electrode system and grounding electrode conductor installation. Meter base sealed and they are not located in either disconnecting means.
ELE19-01886 Temporary Service5/22/20195/22/20195/22/2019 8:16:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok