Inspections for the day of: Wednesday, May 23, 2001.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-01636 Rough-In Permanent Service5/22/20015/23/20015/23/2001 12:00:00 AMAPASS
steve- ###-#### re-insp r/i & per p/s u/g new ok r/i ok 5/23/2001 9:15:42 AM
ELE01-01502 Electrical Rough-In5/22/20015/23/20015/23/2001 12:00:00 AMAPART
underground coty ###-#### u/g ok noted , that contractor needs to watch the bends in pvc conduit, too many zig zags 5/23/2001 12:57:52 PM
ELE01-01687 Temporary Service5/22/20015/23/20015/23/2001 12:00:00 AMAFAIL
cor. posted notified contractor see jf for details 5/23/2001 10:38:34 AM
ELE01-01686 Electrical Rough-In5/22/20015/23/20015/23/2001 12:00:00 AMAPART
underground keri ###-#### duplex sewage lift station & equipment u/g ok called need documentation on classified location 5/23/2001 9:54:24 AM
ELE01-01409 Electrical Rough-In5/23/20015/23/20015/23/2001 12:00:00 AMAPART
Added by Inspector: 315 On 5/23/2001 9:30:57 AM r/i for bath and laundry rm ok
ELE01-01670 Electrical Rough-In5/23/20015/23/20015/23/2001 12:00:00 AMPPASS
mike ###-#### please call before going out ok 5/23/2001 1:45:54 PM
ELE01-00894 Final5/23/20015/23/20015/23/2001 12:00:00 AMPPASS
Jeff ###-#### ok 5/23/2001 2:37:13 PM
ELE01-01674 Final5/23/20015/23/20015/23/2001 12:00:00 AMPFAIL
Ron ###-#### 5/23/2001 2:59:20 PM cor. posted called 250-64(e), 384-16, 250-104(a), boise code 4-05-09 remove romex between service and old panel(j box) 336-6 remove or protect romex on outside of shack 5/23/2001 3:03:14 PM
ELE01-01471 Rough-In Permanent Service5/23/20015/23/20015/23/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 05/23/2001 at 10:22:00. Contact: ###-####. p/s u/g new ok r/i ok 5/23/2001 2:04:19 PM
ELE01-00828 Permanent Service5/23/20015/23/20015/23/2001 12:00:00 AMPFAIL
Mike ###-#### called talked with contractor bond water system, install GEC in their own conduits and uncover u/g that was covered before inspection 5/23/2001 4:56:22 PM