FIR03-00130
| INSP-Final Inspection | 5/23/2003 | 5/23/2003 | 5/23/2003 12:00:00 AM | P | NR |
|
|
###-#### pre telecon with Mike H., the alarms are not ready to verify signal to panel and he will reschedule when they are ready 5/23/2003 1:36:23 PM
|
FIR02-00005
| INSP-Sprinkler Rough-in/Hydro | 5/23/2003 | 5/23/2003 | 5/23/2003 12:00:00 AM | P | PART |
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore tripped dry system to baggae handling area - trip time 1 minute; tampers and low air didn't report to fire panel; will need to reverify these signals for proper monitoring 5/23/2003 2:21:32 PM
|
BLD03-00776
| FIRE-Final Inspection | 5/23/2003 | 5/23/2003 | 5/23/2003 12:00:00 AM | P | NR |
|
|
shannon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore met with the GC as they weren't ready for a final; exit signs need to be tested; exit doors to the east and west to be openable from the inside without special knowledge; hang extinguisher at east exit; kitchen area was exsisting and now work was performed in this area; will need to mount the K class extinguisher 5/23/2003 3:14:01 PM
|
FIR03-00180
| INSP-Final Inspection | 5/23/2003 | 5/23/2003 | 5/23/2003 12:00:00 AM | P | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|