Inspections for the day of: Friday, May 23, 2003.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00130 INSP-Final Inspection5/23/20035/23/20035/23/2003 12:00:00 AMPNR
###-#### pre telecon with Mike H., the alarms are not ready to verify signal to panel and he will reschedule when they are ready 5/23/2003 1:36:23 PM
FIR02-00005 INSP-Sprinkler Rough-in/Hydro5/23/20035/23/20035/23/2003 12:00:00 AMPPART
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore tripped dry system to baggae handling area - trip time 1 minute; tampers and low air didn't report to fire panel; will need to reverify these signals for proper monitoring 5/23/2003 2:21:32 PM
BLD03-00776 FIRE-Final Inspection5/23/20035/23/20035/23/2003 12:00:00 AMPNR
shannon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore met with the GC as they weren't ready for a final; exit signs need to be tested; exit doors to the east and west to be openable from the inside without special knowledge; hang extinguisher at east exit; kitchen area was exsisting and now work was performed in this area; will need to mount the K class extinguisher 5/23/2003 3:14:01 PM
FIR03-00180 INSP-Final Inspection5/23/20035/23/20035/23/2003 12:00:00 AMPPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore