ELE05-01765
| Final | 5/23/2005 | 5/23/2005 | 5/23/2005 4:24:24 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
|
ELE05-01814
| Electrical Rough-In | 5/23/2005 | 5/23/2005 | 5/23/2005 3:33:02 PM | P | PART |
|
|
underground inspection///jeremy ###-#### u/g for outside except main entry into property ok to cover
|
ELE05-01799
| Temporary Service | 5/23/2005 | 5/23/2005 | 5/23/2005 2:53:24 PM | P | FAIL |
|
|
###-#### - dan called tried to leave message, couldn't get through, 250.53(G) the upper end of the electrode shall be flush with or below ground unless protected, 406.5 receptacle covers shall completely cover the opening and seat against the mount
|
ELE05-01800
| Electrical Rough-In | 5/23/2005 | 5/23/2005 | 5/23/2005 2:36:09 PM | P | FAIL |
|
|
###-#### - dan - Note: cover 314.17(A) openings shall be closed where conductors enter(can lights), 314.20, in walls of combustible material, boxes shall be flush with finished surface(so garage lite), 250.148(C) metal boxes shall be grounded, BC
|
ELE05-01800
| Permanent Service | 5/23/2005 | 5/23/2005 | 5/23/2005 2:30:38 PM | P | FAIL |
|
|
###-#### - dan 312.5 conductors entering enclosures shall be protected from abrasion (gec into panel)
|
ELE05-01630
| Electrical Rough-In | 5/23/2005 | 5/23/2005 | 5/23/2005 1:32:59 PM | P | PASS |
|
|
Under slab raceways; Phone #: ###-#### Internet Inspection Request from: Nikki Day under slab conduit for south (gym) ok to cover
|
ELE05-01794
| Temporary Service | 5/20/2005 | 5/23/2005 | 5/23/2005 9:49:15 AM | A | PASS |
|
|
ron ###-#### t/s u/g n ok
|
ELE05-01808
| Rough-In Permanent Service | 5/23/2005 | 5/23/2005 | 5/23/2005 9:48:32 AM | P | PASS |
|
|
clyde ###-#### called contr about mbr recpt, he said they build pony wall after set tub, the mount rcpt. ric ok. p/s u/g n ok
|
ELE05-01790
| Temporary Service | 5/20/2005 | 5/23/2005 | 5/23/2005 9:03:55 AM | A | PASS |
|
|
ron ###-#### called left message about labels. t/s u/g n ok
|
ELE05-01793
| Temporary Service | 5/20/2005 | 5/23/2005 | 5/23/2005 8:48:37 AM | A | PASS |
|
|
ron ###-#### called left message about labels. t/s u/g n ok
|
ELE05-01792
| Temporary Service | 5/20/2005 | 5/23/2005 | 5/23/2005 8:46:38 AM | A | PASS |
|
|
ron ###-#### called ,left message about labels t/s u/g n ok
|
ELE05-01791
| Temporary Service | 5/20/2005 | 5/23/2005 | 5/23/2005 8:28:16 AM | A | PASS |
|
|
ron ###-#### called, left message about labels. t/s u/g n ok
|
ELE05-01226
| Electrical Rough-In | 5/21/2005 | 5/23/2005 | 5/23/2005 8:17:38 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/21/2005 at 9:51:10 AM. Contact: ###-####. potting only ok 2 fixtures
|