FIR05-00105
| INSP-Final Inspection | 5/12/2005 | 5/23/2005 | 5/23/2005 6:40:50 PM | P | PASS |
|
|
Fire alarm finaled.
|
FIR05-00196
| INSP-Final Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 4:18:48 PM | P | PASS |
|
|
Fire alarm finaled.
|
FIR05-00154
| INSP-Final Inspection | 5/20/2005 | 5/23/2005 | 5/23/2005 4:17:29 PM | P | FAIL |
|
|
Pendent heads in hallway need to match response rating per NFPA 13 8.3.3.2. Upright heads above spray room are overspaced, need to meet 130 sq foot req. Perform hydrostatic test per. review notes.
|
FIR04-00811
| INSP-Final Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 1:12:23 PM | P | FAIL |
|
|
Q.R.E.C G.B heads in one compartment of bank vault are mixed with a solder link head in the same compartment, verify if response time is the same to meet NFPA 8.3.3.2. Verify if vault area is indeed LH, it appears to be used as storage.
|
BLD05-00053
| FIRE-Final Inspection | 5/20/2005 | 5/23/2005 | 5/23/2005 12:41:23 PM | P | CANC |
|
|
Duplicate inspection, was meant for alarms already called in, per Dave GC.
|
BLD05-00497
| FIRE-Final Inspection | 5/20/2005 | 5/23/2005 | 5/23/2005 12:09:35 PM | P | FAIL |
|
|
Need approved hardware on main entry/exits facing main st., repair two exit signs and test remaining signs, need all door hardware installed to verify operation, test emergency lighting, verify if duct detectors are installed, review remaining life safety
|
BLD05-00053
| FIRE-Alarm Testing | 5/20/2005 | 5/23/2005 | 5/23/2005 10:39:28 AM | A | FAIL |
|
|
Fail inspection, alarm and fire sprinkler need inspection and sign-off prior to bld. permit final. This inspection was for life safety final, of which several outstanding issues still need addresed.
|
MIS05-00070
| FIR-Final | 5/20/2005 | 5/23/2005 | 5/23/2005 8:29:31 AM | A | CANC |
|
|
tyson; Phone #: ###-#### Cancel inspection per Tyson, not ready.
|
BLD05-00497
| FIRE-Final Inspection | 5/20/2005 | 5/23/2005 | 5/23/2005 12:00:00 AM | A | CANC |
|
|
or ###-####///jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore--need insp for the pm
|
FIR04-00723
| INSP-Final Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|
BLD04-03033
| FIRE-Final Inspection | 5/23/2005 | 5/23/2005 | 5/23/2005 12:00:00 AM | P | PASS |
|
|
HVAC Liebert shutdown upon smoke detection. Inspection satisfactory.
|