Inspections for the day of: Monday, May 23, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00105 INSP-Final Inspection5/12/20055/23/20055/23/2005 6:40:50 PMPPASS
Fire alarm finaled.
FIR05-00196 INSP-Final Inspection5/23/20055/23/20055/23/2005 4:18:48 PMPPASS
Fire alarm finaled.
FIR05-00154 INSP-Final Inspection5/20/20055/23/20055/23/2005 4:17:29 PMPFAIL
Pendent heads in hallway need to match response rating per NFPA 13 8.3.3.2. Upright heads above spray room are overspaced, need to meet 130 sq foot req. Perform hydrostatic test per. review notes.
FIR04-00811 INSP-Final Inspection5/23/20055/23/20055/23/2005 1:12:23 PMPFAIL
Q.R.E.C G.B heads in one compartment of bank vault are mixed with a solder link head in the same compartment, verify if response time is the same to meet NFPA 8.3.3.2. Verify if vault area is indeed LH, it appears to be used as storage.
BLD05-00053 FIRE-Final Inspection5/20/20055/23/20055/23/2005 12:41:23 PMPCANC
Duplicate inspection, was meant for alarms already called in, per Dave GC.
BLD05-00497 FIRE-Final Inspection5/20/20055/23/20055/23/2005 12:09:35 PMPFAIL
Need approved hardware on main entry/exits facing main st., repair two exit signs and test remaining signs, need all door hardware installed to verify operation, test emergency lighting, verify if duct detectors are installed, review remaining life safety
BLD05-00053 FIRE-Alarm Testing5/20/20055/23/20055/23/2005 10:39:28 AMAFAIL
Fail inspection, alarm and fire sprinkler need inspection and sign-off prior to bld. permit final. This inspection was for life safety final, of which several outstanding issues still need addresed.
MIS05-00070 FIR-Final5/20/20055/23/20055/23/2005 8:29:31 AMACANC
tyson; Phone #: ###-#### Cancel inspection per Tyson, not ready.
BLD05-00497 FIRE-Final Inspection5/20/20055/23/20055/23/2005 12:00:00 AMACANC
or ###-####///jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore--need insp for the pm
FIR04-00723 INSP-Final Inspection5/23/20055/23/20055/23/2005 12:00:00 AMPPASS
Fire sprinkler finaled.
BLD04-03033 FIRE-Final Inspection5/23/20055/23/20055/23/2005 12:00:00 AMPPASS
HVAC Liebert shutdown upon smoke detection. Inspection satisfactory.