Inspections for the day of: Tuesday, May 23, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01816 Conference5/23/20065/23/20065/23/2006 5:33:35 PMPDONE
conference ok p/s still all messed up corr. not made met electrician
ELE06-01523 Electrical Rough-In5/23/20065/23/20065/23/2006 5:17:01 PMPFAIL
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy need to meet contractor box fill screws in plastic boxes,broken clamps cutin boxes, recept spacing kit ,D W, disposal circuits
ELE06-01849 Permanent Service5/23/20065/23/20065/23/2006 5:02:35 PMPNR
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s repaired to get power back on from wind damage, owner will get bids to have service broght up to code, grding, needs main disconnect, and address old p/s as sub panels
ELE06-00856 Electrical Rough-In5/23/20065/23/20065/23/2006 3:33:07 PMPPART
ok to cover-- dave-gate 560 add 4632 aeronca-on south end of airport -call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
u/g ok
ELE06-01873 Permanent Service5/23/20065/23/20065/23/2006 3:05:01 PMPNR
per jack frank for today--kevin-- ###-#### call 1st before insp p/s not ready corrections conference only, needs 4 locknuts for each rigid nipple 300.10&12, 250.52(A)(1)for grding 250.104(A)(1) if bonding,240.24 breakers over 6ft 7"
ELE06-01823 Electrical Rough-In5/22/20065/23/20065/23/2006 2:26:25 PMPFAIL
TIM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. 300.4(A)(1)&(D), 600.5 sign circuit, panel clearence
ELE06-01822 Electrical Rough-In5/22/20065/23/20065/23/2006 2:25:37 PMPFAIL
TIM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. 300.4(A)(1)&(D), 600.5 sign circuit, panel clearence
ELE06-01821 Electrical Rough-In5/22/20065/23/20065/23/2006 2:24:43 PMPFAIL
TIM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. 300.4(A)(1)&(D), 600.5 sign circuit, panel clearence
ELE06-01810 Electrical Rough-In5/22/20065/23/20065/23/2006 2:23:39 PMPFAIL
TIM; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called panel clearence, 600.5 sign circuit, 300.4 (A)(1)&(D)
ELE06-01592 Permanent Service5/23/20065/23/20065/23/2006 1:13:05 PMPPASS
ground is fixed. thanks jack, bill; Phone #: ###-#### Internet Inspection Request from: Bob Glenn p/s u/g new ok
ELE06-01788 Temporary Service5/22/20065/23/20065/23/2006 12:41:28 PMAFAIL
Scheduled by a contractor via Hello! on 5/22/2006 at 2:08:42 PM. Contact: ###-####. corr. called conn. for GEC, terminate GEC to neutral bus or lug in meterbase
ELE06-00380 Electrical Rough-In5/22/20065/23/20065/23/2006 12:18:22 PMAPART
Scheduled by a contractor via Hello! on 5/22/2006 at 1:33:22 PM. Contact: ###-####. floor heat ok
ELE06-01677 Rough-In Permanent Service5/23/20065/23/20065/23/2006 10:17:58 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson need approved plans, is it a single fam dwelling ,duplex, apartment ? needs all makeup complete, 300.4 nail plates and 11/4" high and low voltage called
ELE06-01825 Temporary Service5/22/20065/23/20065/23/2006 9:12:11 AMAFAIL
adam-- ###-#### corr. called 110.3 use
sq D breaker not GE, grd rod driven at less than 45 degree angle
ELE06-01816 Permanent Service5/22/20065/23/20065/23/2006 8:44:52 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer corr. called 250.64(C&E) splices in GEC needs listed grd fittings for GEC at meterbase and both ends of nipple250.24 terminate GEC to neutral 230.24(A) needs 8ft over roof, 110.12(A) seal KOs, note sheath of cable not in conn, rigid requires locknuts both inside and outside , remove old GEC that is spliced in panel, is hot and cold bonded, had no acces into meter base, partial correction notice only need too talk with electrician called no response C O W