ELE06-00482
| Rough-In Permanent Service | 5/23/2006 | 5/23/2006 | 5/23/2006 4:27:51 PM | P | NH |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, door locked, needs to call later
|
ELE05-02630
| Permanent Service | 5/22/2006 | 5/23/2006 | 5/23/2006 3:58:46 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters bld says no electrical planned for bldg, talked to contr, told to get permits in order for an inspection
|
ELE06-01336
| Final | 5/23/2006 | 5/23/2006 | 5/23/2006 3:27:52 PM | P | PASS |
|
|
###-#### - doug ok to final
|
ELE06-01409
| Final | 5/23/2006 | 5/23/2006 | 5/23/2006 2:29:23 PM | P | FAIL |
|
|
ethan - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, nec 210.12(B) all 120v 15 and 20A branch circuits supplying outlets in dwelling unit bedrooms shall be protected by a listed arc-fault circuit interrupter, 314.20 in walls of combustible material box shall be flush with finished surface, 314.21 drywall shall be finished so there are no gaps greater than 1/8", 406.5 faceplates shall be installed to completely cover opening and seat against surface, 406.4(D) recpts shall be flush with or project from faceplates
|
ELE06-01840
| Final | 5/23/2006 | 5/23/2006 | 5/23/2006 1:52:24 PM | P | PASS |
|
|
lona; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec ok
|
ELE05-01308
| Final | 5/23/2006 | 5/23/2006 | 5/23/2006 1:22:44 PM | P | PASS |
|
|
stonemill deli suite 104-tom; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final, signed occ card
|
ELE06-01773
| Final | 5/22/2006 | 5/23/2006 | 5/23/2006 11:37:19 AM | A | PASS |
|
|
need final inspection on new 200 amp service. please call Page Sausman to meet @ ###-####. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
|
ELE06-01773
| Permanent Service | 5/23/2006 | 5/23/2006 | 5/23/2006 11:36:53 AM | A | PASS |
|
|
need final inspection on new 200 amp service. please call Page Sausman to meet @ ###-####. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g rec ok
|
ELE05-04387
| Electrical Rough-In | 5/22/2006 | 5/23/2006 | 5/23/2006 10:26:39 AM | A | PASS |
|
|
ceiling insp- nathan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to cover ceiling
|
ELE06-01835
| Temporary Service | 5/22/2006 | 5/23/2006 | 5/23/2006 10:09:23 AM | A | FAIL |
|
|
joe-- ###-####-- for a temp pole called contr, left corr notice, nec 110.12(A) unused openings shall be closed, 110.12(C) there shall be no broken parts, 230.26 in no case shall service conductors be less than 10' above finished grade, 110.14(A) connections of conductors to terminals shall ensure thoroughly good connections, 110.26(A) work space shall be provided about equipment
|
ELE05-04271
| Final | 5/22/2006 | 5/23/2006 | 5/23/2006 9:50:48 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Eric Shaner ok to final
|
ELE06-00833
| Electrical Rough-In | 5/22/2006 | 5/23/2006 | 5/23/2006 9:02:46 AM | A | PASS |
|
|
gill- call 1/2 hr before insp ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to cover ceiling only
|
ELE06-01807
| Electrical Rough-In | 5/22/2006 | 5/23/2006 | 5/23/2006 8:12:56 AM | A | CANC |
|
|
rough-in inspection as early as possible on 05/23 a.m. Contact is Greg ###-####. Thanks.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie request cancel due to saw cutting problems, called contr to verify. Will recall ltr.
|