Inspections for the day of: Tuesday, May 23, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00208 INSP-Sprinkler Rough-in/Hydro5/22/20065/23/20065/24/2006 10:11:23 AMPCANC
Cancel inspection per contractor, to be rescheduled when ready.
FIR06-00206 INSP-Sprinkler Rough-in/Hydro5/22/20065/23/20065/24/2006 10:10:34 AMPFAIL
Access to the tenant space was not made available, no inspection performed.
FIR06-00207 INSP-Sprinkler Rough-in/Hydro5/22/20065/23/20065/24/2006 10:09:20 AMPFAIL
The portion of install at the two new heads in the basement soffit has been concealed prior to inspection, also need to provide as-builts reflecting field changes for piping supply to new heads.
FIR06-00203 INSP-Final Inspection5/18/20065/23/20065/23/2006 3:37:04 PMAPASS
Fire alarm passed final field inspection.
FIR05-00482 INSP-Final Inspection5/19/20065/23/20065/23/2006 3:36:20 PMAPASS
As-builts for address changes verified on site, permit finaled.
FIR05-00871 INSP-Final Inspection5/19/20065/23/20065/23/2006 3:35:17 PMAPASS
Fire sprinkler work is satisfactory, drain calculations provided, permit finaled.
FIR05-00454 INSP-Conference5/22/20065/23/20065/23/2006 3:33:03 PMADONE
On site discussion regarding work in progress for the permit.
FIR06-00287 INSP-Sprinkler Rough-in5/22/20065/23/20065/23/2006 1:19:49 PMPFAIL
Two heads as installed in the NE room of the tenant area are overspaced from an adjacent wall, also need to provide as-builts reflecting two deleted heads.
FIR06-00326 INSP-Final Inspection5/22/20065/23/20065/23/2006 12:54:21 PMPPART
Project is not ready for final inspection as walls and ceilings which create the separation between sprinklers are not complete at this time. Overhead rough-in is acceptable for cover.
FIR06-00320 INSP-Sprinkler Rough-in5/23/20065/23/20065/23/2006 12:19:42 PMPFAIL
One head at the 1st floor dining area is too close to a heat diffuser, two heads in the master bath 1st floor do not meet min. separation distances required, two drops are not installed in the main level bedroom, be aware of possible light fixture obstructions that may develop after fixture installation, one drop is missing in the basement hall, the supply, BFP, and riser are not installed at this time. Tenting for cold cavity protection appears adequate.
BLD05-01869 FIRE-Sprinkler Rough-in5/22/20065/23/20065/23/2006 12:11:44 PMADEFR
This inspection request was for the fire sprinkler permit incorrectly called in under the BLD permit number. See comments for this inpection under FIR06-00320.
FIR06-00111 INSP-Final Inspection5/19/20065/23/20065/23/2006 11:17:47 AMAPASS
Fire alarm work is satisfactory, inspection passed, permit finaled.
FIR05-00285 INSP-Final Inspection5/22/20065/23/20065/23/2006 11:16:52 AMAPASS
Fire alarm work passed final inspection, one existing SD within the TI space is too close to an HVAC diffuser-head to be relocated and verified for approval at life safety inspection.
FIR05-00403 FIR-Aging Inspection5/23/20065/23/20065/23/2006 9:49:47 AM DONE
Building is still under construction, work in progress.
FIR05-00118 INSP-Final Inspection5/23/20065/23/20065/23/2006 9:46:59 AMPPASS
Fire alarm passed inspection, permit not "doc" finaled as previous inspection request was for alarm testing not final inspection.
FIR05-00516 INSP-Final Inspection5/23/20065/23/20065/23/2006 9:45:16 AMPPASS
Fire alarm passed inspection, permit not "doc" finaled as previous inspection request was for alarm testing not final inspection.
FIR05-00082 INSP-Final Inspection5/23/20065/23/20065/23/2006 9:43:04 AMPPASS
Fire alarm passed inspection, permit not "doc" finaled as previous inspection request was for alarm testing not final inspection.