Inspections for the day of: Wednesday, May 23, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS05-00071 MIS-Aging Inspection5/23/20075/23/20075/29/2007 3:53:23 PM FAIL
Temp. use has exceeded the allowed 180 days.
BLD07-00351 FIRE-Final Inspection5/23/20075/23/20075/23/2007 7:38:22 PMPNR
Need to final project related hood suppression permit prior to life safety inspection final.
BLD06-02700 FIRE-Final Inspection5/23/20075/23/20075/23/2007 7:36:00 PMPFAIL
Missing escutcheons at fire sprinkler heads at various locations in the corridors, some heads are in need of adjustment as the deflector is above or even with the ceiling tile, need to repair emergency lighting at several locations, missing a/v fire alarm notification for ADA room 516.
FIR05-00822 INSP-Sprinkler Rough-in/Hydro5/22/20075/23/20075/23/2007 7:31:36 PMPPART
Dry system air test passed within the allowable leakage amount, system lost 1/2 psi over 24 hrs.
BLD07-00094 FIRE-Final Inspection5/22/20075/23/20075/23/2007 2:13:25 PMAPASS
Fire life safety inspection passed, noted all ceiling tile and FS escutcheons are to be installed prior to building structural final as agreed.
FIR06-00645 INSP-Final Inspection5/21/20075/23/20075/23/2007 1:58:32 PMAFAIL
One a/v in the corridor is non-functional, dampers at two locations in the corridor did not close upon alarm condition, noted one relocated manual pull station is installed too high, one set of double doors is out of adjustment at the mag locks, fire dampers on zone 6 did not function upon smoke detection.
FIR07-00225 INSP-Final Inspection5/23/20075/23/20075/23/2007 1:45:57 PMAPASS
Required correction verified, fire sprinkler permit finaled.
FIR06-00800 INSP-Sprinkler Rough-in5/22/20075/23/20075/23/2007 1:42:37 PMAPART
Begin 24 hr. air test of the dry system at 9:00am @ 40psi.
BLD06-01669 FIRE-Final Inspection5/22/20075/23/20075/23/2007 1:38:20 PMAFAIL
Missing exit discharge lighting as shown on approved plans, need visual indicator at the storefront door.
BLD07-00335 FIRE-Final Inspection5/22/20075/23/20075/23/2007 12:50:05 PMAFAIL
Missing exit discharge lights, provide visual indicator at the main entry/exit door, provide correct signage above the keyed locking door, remove deadbolt at the interior vestibule door, building address needs to be contrasting.
FIR07-00430 INSP-Sprinkler Rough-in5/22/20075/23/20075/23/2007 12:46:36 PMAFAIL
UG supply pipe could not be verified for proper installation due to trench collapse and excessive water over the pipe.
FIR05-00536 INSP-Sprinkler Rough-in5/22/20075/23/20075/23/2007 12:44:31 PMAPART
The first floor lobby grid ceiling areas next to the donor walls are approved for cover, noted two heads spaced beyond max. allowabe distance- contractor to relocate one head to eliminate this problem.
FIR07-00456 INSP-Sprinkler Rough-in5/22/20075/23/20075/23/2007 12:40:55 PMAPART
OH fire sprinkler modifications are okay for cover at the drop ceilings.
FIR06-00006 INSP-Final Inspection5/23/20075/23/20075/23/2007 12:39:46 PMAFAIL
Mixed response heads in the same fire area.
BLD06-00443 FIRE-Final Inspection5/22/20075/23/20075/23/2007 12:37:48 PMAFAIL
Provide panic hardware at the second non-required exit or remove the exit signage at this location, the fire sprinkler permit must be finaled prior to BLD final.
BLD04-00943 FIRE-Final Inspection5/22/20075/23/20075/23/2007 12:34:42 PMAPASS
Fire life safety is acceptable for final.
BLD06-02700 FIRE-Sprinkler Rough-in5/22/20075/23/20075/23/2007 12:00:00 AMPCANC
barak ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie