MIS05-00071
| MIS-Aging Inspection | 5/23/2007 | 5/23/2007 | 5/29/2007 3:53:23 PM | | FAIL |
|
|
Temp. use has exceeded the allowed 180 days.
|
BLD07-00351
| FIRE-Final Inspection | 5/23/2007 | 5/23/2007 | 5/23/2007 7:38:22 PM | P | NR |
|
|
Need to final project related hood suppression permit prior to life safety inspection final.
|
BLD06-02700
| FIRE-Final Inspection | 5/23/2007 | 5/23/2007 | 5/23/2007 7:36:00 PM | P | FAIL |
|
|
Missing escutcheons at fire sprinkler heads at various locations in the corridors, some heads are in need of adjustment as the deflector is above or even with the ceiling tile, need to repair emergency lighting at several locations, missing a/v fire alarm notification for ADA room 516.
|
FIR05-00822
| INSP-Sprinkler Rough-in/Hydro | 5/22/2007 | 5/23/2007 | 5/23/2007 7:31:36 PM | P | PART |
|
|
Dry system air test passed within the allowable leakage amount, system lost 1/2 psi over 24 hrs.
|
BLD07-00094
| FIRE-Final Inspection | 5/22/2007 | 5/23/2007 | 5/23/2007 2:13:25 PM | A | PASS |
|
|
Fire life safety inspection passed, noted all ceiling tile and FS escutcheons are to be installed prior to building structural final as agreed.
|
FIR06-00645
| INSP-Final Inspection | 5/21/2007 | 5/23/2007 | 5/23/2007 1:58:32 PM | A | FAIL |
|
|
One a/v in the corridor is non-functional, dampers at two locations in the corridor did not close upon alarm condition, noted one relocated manual pull station is installed too high, one set of double doors is out of adjustment at the mag locks, fire dampers on zone 6 did not function upon smoke detection.
|
FIR07-00225
| INSP-Final Inspection | 5/23/2007 | 5/23/2007 | 5/23/2007 1:45:57 PM | A | PASS |
|
|
Required correction verified, fire sprinkler permit finaled.
|
FIR06-00800
| INSP-Sprinkler Rough-in | 5/22/2007 | 5/23/2007 | 5/23/2007 1:42:37 PM | A | PART |
|
|
Begin 24 hr. air test of the dry system at 9:00am @ 40psi.
|
BLD06-01669
| FIRE-Final Inspection | 5/22/2007 | 5/23/2007 | 5/23/2007 1:38:20 PM | A | FAIL |
|
|
Missing exit discharge lighting as shown on approved plans, need visual indicator at the storefront door.
|
BLD07-00335
| FIRE-Final Inspection | 5/22/2007 | 5/23/2007 | 5/23/2007 12:50:05 PM | A | FAIL |
|
|
Missing exit discharge lights, provide visual indicator at the main entry/exit door, provide correct signage above the keyed locking door, remove deadbolt at the interior vestibule door, building address needs to be contrasting.
|
FIR07-00430
| INSP-Sprinkler Rough-in | 5/22/2007 | 5/23/2007 | 5/23/2007 12:46:36 PM | A | FAIL |
|
|
UG supply pipe could not be verified for proper installation due to trench collapse and excessive water over the pipe.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 5/22/2007 | 5/23/2007 | 5/23/2007 12:44:31 PM | A | PART |
|
|
The first floor lobby grid ceiling areas next to the donor walls are approved for cover, noted two heads spaced beyond max. allowabe distance- contractor to relocate one head to eliminate this problem.
|
FIR07-00456
| INSP-Sprinkler Rough-in | 5/22/2007 | 5/23/2007 | 5/23/2007 12:40:55 PM | A | PART |
|
|
OH fire sprinkler modifications are okay for cover at the drop ceilings.
|
FIR06-00006
| INSP-Final Inspection | 5/23/2007 | 5/23/2007 | 5/23/2007 12:39:46 PM | A | FAIL |
|
|
Mixed response heads in the same fire area.
|
BLD06-00443
| FIRE-Final Inspection | 5/22/2007 | 5/23/2007 | 5/23/2007 12:37:48 PM | A | FAIL |
|
|
Provide panic hardware at the second non-required exit or remove the exit signage at this location, the fire sprinkler permit must be finaled prior to BLD final.
|
BLD04-00943
| FIRE-Final Inspection | 5/22/2007 | 5/23/2007 | 5/23/2007 12:34:42 PM | A | PASS |
|
|
Fire life safety is acceptable for final.
|
BLD06-02700
| FIRE-Sprinkler Rough-in | 5/22/2007 | 5/23/2007 | 5/23/2007 12:00:00 AM | P | CANC |
|
|
barak ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|