Inspections for the day of: Friday, May 23, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01272 Final5/23/20085/23/20085/23/2008 3:48:57 PMPPASS
final on hot tub wiring, any questions call George @ ###-####, Okay to go in backyard to look at. Phone #: ###-#### Internet Inspection Request from: Andy Rose ok
ELE07-02379 Final5/22/20085/23/20085/23/2008 3:09:11 PMPPASS
Garage entrance code 1968E Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok
ELE08-01339 Electrical Rough-In5/22/20085/23/20085/23/2008 2:06:17 PMPFAIL
stu Phone #: ###-#### fail called needs #6awg per manufacture, bond emt and foof metal called left message
ELE08-01372 Electrical Rough-In5/23/20085/23/20085/23/2008 1:18:42 PMPPART
jeff note: bonding/underground Phone #: ###-#### ok no E grid
ELE08-01351 Final5/23/20085/23/20085/23/2008 12:35:58 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see added r/i p/s
ELE08-01351 Rough-In Permanent Service5/23/20085/23/20085/23/2008 12:35:35 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corr called 210.52(C) outlets required for countertops left and right of refer, 210.52(B) remove outlet in hallway to garage from small appliance branch circuit, 110.3(B) shall prive 30"x15" access for jtub per manufactures instructions, 110.3(A) wire all vacuum outlet note shall not be on kit or bath circuits,300.15 ent at low voltage cabinet shall terminate in connectors
ELE07-03838 Final5/22/20085/23/20085/23/2008 10:43:19 AMAPASS
Scheduled by a contractor via Hello! on 5/22/2008 at 10:25:42 AM. Contact: ###-####. survey gfci for disposal recepts, 314.3 bond bushinf for emt in plastic sprinkler control box called final ok card signed
ELE08-00902 Rough-In Permanent Service5/23/20085/23/20085/23/2008 9:27:44 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2008 at 6:39:50 AM. Contact: ###-####. p/s u/g new ok
ELE08-00901 Rough-In Permanent Service5/23/20085/23/20085/23/2008 9:27:22 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2008 at 6:38:32 AM. Contact: ###-####. p/s u/g new ok
ELE08-00539 Rough-In Permanent Service5/23/20085/23/20085/23/2008 9:26:53 AMAPART
Scheduled by a contractor via Hello! on 5/23/2008 at 6:37:14 AM. Contact: ###-####. r/i ok
ELE08-01369 Electrical Rough-In5/22/20085/23/20085/23/2008 8:43:18 AMAPART
Inspection for Bonding of the exponential pool grid. Contact is Jay Sprik. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
ELE08-01340 Conference5/21/20085/23/20085/23/2008 8:15:07 AMADONE
marvin - Phone #: ###-#### ok answered questions, told owner if questions call