ELE08-00115
| Final | 5/22/2008 | 5/23/2008 | 5/23/2008 4:07:53 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 5/22/2008 at 11:29:39 AM. Contact: ###-####. inspection ok, need to make correction on core and shell, then sign card
|
ESC07-00003
| General Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 3:37:21 PM | P | PASS |
|
|
looked ok
|
ESC08-00366
| General Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 3:36:14 PM | P | PASS |
|
|
looked ok
|
ESC08-00345
| General Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 3:33:09 PM | P | PASS |
|
|
looked ok
|
ESC08-00092
| General Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 3:32:01 PM | P | PASS |
|
|
looked ok
|
ELE08-00114
| Final | 5/22/2008 | 5/23/2008 | 5/23/2008 2:43:22 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/22/2008 at 11:31:01 AM. Contact: ###-####. called contractor, left correction notice, NEC 314.23(C) enclosure mounted in finished surface shall be rigidly secured ( over refrigerator space), BCC shall provide pigtail for disposal
|
ELE08-00116
| Final | 5/22/2008 | 5/23/2008 | 5/23/2008 1:55:19 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/22/2008 at 11:28:26 AM. Contact: ###-####. called contractor, left correction notice, NEC 210.63 shall provide convenience (gfci) receptacle within 25' of air conditioner at east end
|
ELE08-00990
| Final | 5/23/2008 | 5/23/2008 | 5/23/2008 1:14:14 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Scott Abbott called contractor, ok to final
|
ELE08-01371
| Temporary Service | 5/23/2008 | 5/23/2008 | 5/23/2008 12:25:15 PM | P | PASS |
|
|
jim Phone #: ###-#### called, left message, left survey, NEC 110.12(C) there shall be no broken parts-receptacle, t/s o/h n ok
|
ELE08-01367
| Temporary Service | 5/22/2008 | 5/23/2008 | 5/23/2008 10:40:59 AM | A | FAIL |
|
|
daniel Phone #: ###-#### called contractor, left message, left correction notice, NEC 350.24(A) shall connect grounded service conductor to grounding electrode conductor, 250.53(G) upper end of ground electrode shall be flush with or below ground, BCC shall correct failed esc- sign, etc
|
ESC08-00419
| General Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 10:32:04 AM | A | FAIL |
|
|
left note on correction in t/s panel to correct deficiency per structural inspection
|
ELE08-01277
| Electrical Rough-In | 5/22/2008 | 5/23/2008 | 5/23/2008 9:52:07 AM | A | PASS |
|
|
This is a swimming pool. The inspection needed if for underground. Thanks Phone #: ###-#### Internet Inspection Request from: Chris Weimar u/g ok
|
ELE08-01079
| Electrical Rough-In | 5/22/2008 | 5/23/2008 | 5/23/2008 9:25:32 AM | A | PASS |
|
|
jerod Note: bonding Phone #: ###-#### equipotential grid ok to pour
|
ELE08-01266
| Electrical Rough-In | 5/22/2008 | 5/23/2008 | 5/23/2008 8:39:59 AM | A | PASS |
|
|
reinspect electrical for addition Phone #: ###-#### Internet Inspection Request from: Tim Lawrence corrections made, ric ok
|
ELE08-00506
| Final | 5/23/2008 | 5/23/2008 | 5/23/2008 8:06:17 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Spencer Mclean n corrections made, ok to final, signed occupancy card
|