Inspections for the day of: Friday, May 23, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00365 INSP-Final Inspection5/23/20085/23/20085/23/2008 4:52:51 PMPPASS
K class PFE to be posted as discussed-will verify at life safety final, the hood suppression system functioned properly under test conditions, permit finaled.
BLD07-02935 FIRE-Final Inspection5/22/20085/23/20085/23/2008 4:46:39 PMAFAIL
Need to repair two non-functional EM lights at the kitchen and service area, one HVAC unit failed to shut down upon smoke detection, one EM light at the entry vestibule repaired while on site, remainder of items previously noted are acceptable.
FIR08-00163 INSP-Sprinkler Rough-in5/23/20085/23/20085/23/2008 3:51:22 PMPPART
UG fire supply line approved for cover with the exception of the thrust blocks not yet poured at the 90 and stub-in, also need to provide method for seismic clearance at the ductile riser and floor slab interface.

BLD08-00193 FIRE-Final Inspection5/23/20085/23/20085/23/2008 3:45:30 PMPPART
Site visit performed by S. Rogers. Acceptable for TOC. Maglocks on doors were approved by Mark Senteno, Asst. FM, to not have motion detection release, however, the required manual push button release does not maintain the doors unlocked for the required minimum 30 seconds (Ref IFC 1008.1.3.4 item 3). It relocks immediately upon release of the push button. For Temp Occy approval, the mag lock circuit was electrically bypassed (dedicated circuit breaker tripped, within the locked electrical panel). The P&R contact, Toby, indicated Parks will manually lock and unlock the doors each day, as they currently do at many other facilities, until they get the required timer installed and field approved by PDS/Fire. All other Fire/Life Safety items were satisfactory. SLR.
FIR07-00606 INSP-Sprinkler Rough-in/Hydro5/22/20085/23/20085/23/2008 3:38:45 PMAPART
OH hydrostatic testing for system #4 completed without pressure loss.
BLD06-00014 FIRE-Final Inspection5/22/20085/23/20085/23/2008 3:21:36 PMANR
Inspection rescheduled.
FIR07-00702 INSP-Sprinkler Rough-in5/22/20085/23/20085/23/2008 2:00:04 PMAPART
See approved plans for areas okayed to date.
FIR08-00039 INSP-Final Inspection5/22/20085/23/20085/23/2008 1:07:21 PMACANC
Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Overbooked, inspection rescheduled per phone call to contractor.
FIR08-00168 INSP-Final Inspection5/22/20085/23/20085/23/2008 1:06:32 PMACANC
mike Phone #: ###-#### Overbooked, inspection rescheduled as agreed with sub and general contractors.
FIR07-00997 INSP-Sprinkler Rough-in/Hydro5/22/20085/23/20085/23/2008 12:29:15 PMAPART
Hydrostatic testing for the new system piping branch lines and pendent heads passed.
BLD07-02405 FIRE-Conference5/23/20085/23/20085/23/2008 12:23:54 PMPDONE
Discussion with contractor regarding project schedule and building permit shell and tenant permit approvals prior to elevator completion.
BLD08-00612 FIRE-Final Inspection5/22/20085/23/20085/23/2008 12:00:15 PMAPASS
Fire life safety completed satisfactory, however the building address per permit documents does not match the existing address numbers on the building (3152 per permit, 3156 per actual posted building #'s). Notified contractor to resolve the discrepancy prior to structural final approval for occupancy.
BLD08-00837 FIRE-Final Inspection5/22/20085/23/20085/23/2008 11:56:06 AMAPASS
Fire life safety inspection completed acceptable, no modifications to the fire sprinkler or alarm systems were necessary to complete BLD permit work.
BLD07-02796 FIRE-Final Inspection5/22/20085/23/20085/23/2008 10:58:57 AMAPASS
Main door mag locks tested okay, items on previously issued correction notice verified for compliance, door hardware at conference room #2 to be changed prior to structural final and verified at that time per discussion with contractor, remainder of life safety is satisfactory.
BLD07-02797 FIRE-Final Inspection5/22/20085/23/20085/23/2008 10:54:40 AMAPASS
Correction notice items are finished, life safety passed.
BLD07-02795 FIRE-Final Inspection5/22/20085/23/20085/23/2008 10:53:48 AMAPASS
Building shell life safety inspection passed, notified contractor to install fire lane signage per review notes prior to occupancy approval for the adjacent structure.