ELE12-00227
| ELE-Aging Inspection | 5/23/2014 | 5/23/2014 | 5/29/2014 4:01:39 PM | | DONE |
|
|
Still under construction
|
ELE12-02376
| ELE-Aging Inspection | 5/23/2014 | 5/23/2014 | 5/29/2014 3:50:40 PM | | DONE |
|
|
Spoke to contractor will check
|
ELE12-02290
| Final | 5/22/2014 | 5/23/2014 | 5/23/2014 3:37:31 PM | A | PASS |
|
|
Contact person Jim Snodgrass Phone #: ###-#### >> Inspection requested via web by Todd Sellman Final ok
|
ELE14-01316
| Conference | 5/22/2014 | 5/23/2014 | 5/23/2014 3:27:38 PM | A | FAIL |
|
|
need conference on what is going to be required to repair wiring in kitchen due to fire. Please call Andy @ ###-#### to set time to meet. Phone #: ###-#### >> Inspection requested via web by Andy Rose Due to small kitchen fire ceiling and some drywall has been removed in kitchen. BCC 4-05-32- Code violation not to be retained. When altering pre-existing wiring the electrical witing in close proximity shall be in accordance with present code. 1- NEC 210.8 All kitchen counter top receptical outlets shall have GFCI protection. 2- NEC 210.11(C)(1)- Kitchen counter top receptical outlets shall be fed by a minimum of 2 20 amp small appliance circuits that shall have no other outlets. BCC 4-05-31(C)- Unfused conductors shall not enter a structure. Main fused disconnecting means shall be installed outside as per NEC 230.70 and 230.71. NEC 110.26- Minimum work space shall be 30" wide and 36" deep at panel location.
|
ELE13-03546
| Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 3:10:47 PM | P | FAIL |
|
|
partial basement ceiling - Mike Phone #: ###-#### 300.11 Hard lid support system shall not support light fixtures and boxes unless system is rated for support of additional fixtures.
|
ELE14-01329
| Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 2:49:32 PM | P | PASS |
|
|
Rocky Phone #: ###-#### Walls and hard lid rough in ok cover
|
ELE14-01126
| Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 1:35:14 PM | P | PASS |
|
|
Rocky Phone #: ###-#### Walls and hard lid rough in ok cover
|
ELE14-01330
| Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 12:58:44 PM | P | PASS |
|
|
Warren-around 1 if possible please Phone #: ###-#### Wall rough in ok cover
|
ELE14-01219
| Final | 5/23/2014 | 5/23/2014 | 5/23/2014 12:13:50 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Final ok
|
ELE14-00987
| Final | 5/23/2014 | 5/23/2014 | 5/23/2014 11:30:16 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Terry Scott Final ok
|
ELE14-01310
| Permanent Service | 5/22/2014 | 5/23/2014 | 5/23/2014 11:21:19 AM | A | FAIL |
|
|
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering. Phone #: ###-#### >> Inspection requested via web by Stephen Kren 110.26- Minimum work space of 30" wide and 36" deep shall be provided for panel location. 230.71- Maximum of 6 disconnects for service disconnecting means
|
ELE14-01188
| Electrical Rough-In | 5/23/2014 | 5/23/2014 | 5/23/2014 9:50:56 AM | P | PASS |
|
|
Kelly Phone #: ###-#### Basement and kitchen rewired main level existing. Rough in ok cover
|
ELE14-01319
| Electrical Rough-In | 5/22/2014 | 5/23/2014 | 5/23/2014 9:35:32 AM | A | PASS |
|
|
Please call Lynn Proctor at ###-#### on your way to the site. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor Interior surface conduits and recepticals rough in ok
|
ELE14-01319
| Permanent Service | 5/22/2014 | 5/23/2014 | 5/23/2014 9:34:41 AM | A | PASS |
|
|
Please call Lynn Proctor at ###-#### on your way to the site.. Phone #: ###-#### >> Inspection requested via web by Lynn Proctor p/s u/g n ok
|
ELE14-00537
| Final | 5/22/2014 | 5/23/2014 | 5/23/2014 8:53:43 AM | A | PASS |
|
|
It will be unlocked. Please let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|