ELE13-01353
| ELE-Aging Inspection | 5/23/2016 | 5/23/2016 | 5/31/2016 7:57:04 AM | | CANC |
|
|
too busy
|
ELE16-01632
| Electrical Rough-In | 5/20/2016 | 5/23/2016 | 5/23/2016 2:48:28 PM | P | PASS |
|
|
This inspection is needed for the underground work. Please contact Jamie Winters with questions for the electrical at ###-#### or ###-####. Thank you Phone #: ###-#### Inspection requested via web by JAMIE WINTERS underground from building to propane tank ok cover
|
ELE16-01427
| Electrical Rough-In | 5/23/2016 | 5/23/2016 | 5/23/2016 2:28:39 PM | P | FAIL |
|
|
Please call ahead for access, at least 30min, late afternoon please - John Phone #: ###-#### 300.11 cables and raceways shall not be supported by cieling grids
|
ELE16-01438
| Final | 5/23/2016 | 5/23/2016 | 5/23/2016 1:53:28 PM | P | CANC |
|
|
Chris is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates EC will need to provide a ladder to verify sysmic wires are in place for fixtures that were replaced
|
ELE16-01133
| Final | 5/23/2016 | 5/23/2016 | 5/23/2016 1:39:17 PM | P | FAIL |
|
|
Need final for the hall and ceiling. Call Jimmy for questions ###-#### Phone #: ###-#### Inspection requested via web by John Edwards 110.12 (a) un-used openings shall be closed 406.6 faceplates required
|
ELE16-00978
| Final | 5/20/2016 | 5/23/2016 | 5/23/2016 1:19:33 PM | A | FAIL |
|
|
Any questions please let me know, the key if needed is in a lockbox, code 1225, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren 225.38 (b) each structure or building shall have a means of disc. for all ungrounded conductors and structured wiring Dishwasher needs to be wired and in place (as per conversation with darryl first correction will not be enforced at this time or this job, will look for it on other jobs in the future)
|
ELE16-00755
| Final | 5/23/2016 | 5/23/2016 | 5/23/2016 1:01:08 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 410.10(d) luminaires located with 8' vertically and 3' horizontal of a bathtub rim or shower threshold shall be marked wet located rated 353.30(a) PVC shall be supported within 3' of a cabinet
|
ELE16-01639
| Final | 5/20/2016 | 5/23/2016 | 5/23/2016 8:59:25 AM | A | CANC |
|
|
please call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott needed p/s only
|
ELE16-01639
| Permanent Service | 5/23/2016 | 5/23/2016 | 5/23/2016 8:59:04 AM | P | PASS |
|
|
please call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott p/s u/g n ok
|
ELE16-01643
| Electrical Rough-In | 5/23/2016 | 5/23/2016 | 5/23/2016 8:56:46 AM | A | PASS |
|
|
Garage rough-in. Personal house Call prior to inspection Phone #: ###-#### Inspection requested via web by Jarod Murray Attached garage addition ok cover
|
ELE16-01574
| Final | 5/20/2016 | 5/23/2016 | 5/23/2016 8:22:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by robert feller Service change final ok
|