Inspections for the day of: Monday, May 23, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01353 ELE-Aging Inspection5/23/20165/23/20165/31/2016 7:57:04 AM CANC
too busy
ELE16-01632 Electrical Rough-In5/20/20165/23/20165/23/2016 2:48:28 PMPPASS
This inspection is needed for the underground work. Please contact Jamie Winters with questions for the electrical at ###-#### or ###-####. Thank you Phone #: ###-#### Inspection requested via web by JAMIE WINTERS
underground from building to propane tank ok cover
ELE16-01427 Electrical Rough-In5/23/20165/23/20165/23/2016 2:28:39 PMPFAIL
Please call ahead for access, at least 30min, late afternoon please - John Phone #: ###-####
300.11 cables and raceways shall not be supported by cieling grids
ELE16-01438 Final5/23/20165/23/20165/23/2016 1:53:28 PMPCANC
Chris is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates
EC will need to provide a ladder to verify sysmic wires are in place for fixtures that were replaced
ELE16-01133 Final5/23/20165/23/20165/23/2016 1:39:17 PMPFAIL
Need final for the hall and ceiling. Call Jimmy for questions ###-#### Phone #: ###-#### Inspection requested via web by John Edwards
110.12 (a) un-used openings shall be closed
406.6 faceplates required
ELE16-00978 Final5/20/20165/23/20165/23/2016 1:19:33 PMAFAIL
Any questions please let me know, the key if needed is in a lockbox, code 1225, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
225.38 (b) each structure or building shall have a means of disc. for all ungrounded conductors and structured wiring
Dishwasher needs to be wired and in place
(as per conversation with darryl first correction will not be enforced at this time or this job, will look for it on other jobs in the future)
ELE16-00755 Final5/23/20165/23/20165/23/2016 1:01:08 PMPFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
410.10(d) luminaires located with 8' vertically and 3' horizontal of a bathtub rim or shower threshold shall be marked wet located rated
353.30(a) PVC shall be supported within 3' of a cabinet
ELE16-01639 Final5/20/20165/23/20165/23/2016 8:59:25 AMACANC
please call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott
needed p/s only
ELE16-01639 Permanent Service5/23/20165/23/20165/23/2016 8:59:04 AMPPASS
please call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott
p/s u/g n ok
ELE16-01643 Electrical Rough-In5/23/20165/23/20165/23/2016 8:56:46 AMAPASS
Garage rough-in.
Personal house
Call prior to inspection Phone #: ###-#### Inspection requested via web by Jarod Murray
Attached garage addition ok cover
ELE16-01574 Final5/20/20165/23/20165/23/2016 8:22:22 AMAPASS
Phone #: ###-#### Inspection requested via web by robert feller
Service change final ok