BLD16-01704
| FIRE-Final Inspection | 5/23/2016 | 5/23/2016 | 5/23/2016 3:00:07 PM | P | FAIL |
|
|
Repair or remove the emergency lights, provide one additional fire extinguisher down stairs as discussed.
|
BLD15-01869
| FIRE-Conference | 5/23/2016 | 5/23/2016 | 5/23/2016 2:28:49 PM | P | DONE |
|
|
I performed a life safety inspection. I noted exit signs and emergency lights that are non functional, not all fire extinguishers are mounted and not all of the door hardware is installed. Emergency lights are missing at the east end of the show room, three thumbturn dead bolts need to be removed from office doors, address numbers on three sides of the building need installed, signage at facp/riser and electrical rooms needs installed.
|
BLD15-04296
| FIRE-Final Inspection | 5/23/2016 | 5/23/2016 | 5/23/2016 2:23:14 PM | P | FAIL |
|
|
Provide mounted and tagged fire extinguisher as discussed, Provide approved hardware on the secondary front exit door or get plan review approval to remove hardware and turn the door into a window.
|
NAF16-00037
| INSP-Final | 5/23/2016 | 5/23/2016 | 5/23/2016 12:39:09 PM | P | FAIL |
|
|
Call prior to going Phone #: 5705792 >>
I left two voice messages and went to job site but no contact was made. I spoke with the general contractor and we a rescheduling for tomorrow morning.
|
BLD16-00215
| FIRE-Final Inspection | 5/23/2016 | 5/23/2016 | 5/23/2016 12:36:16 PM | P | FAIL |
|
|
Need the project related fire alarm and hood suppression permits finaled. Also there were no small documents on site. Suite number and Occupant Load sign are missing.
|
NAF15-00045
| INSP-Final | 5/20/2016 | 5/23/2016 | 5/23/2016 12:34:57 PM | A | CANC |
|
|
Tyler is the contact. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
|
NAF15-00044
| INSP-Final | 5/20/2016 | 5/23/2016 | 5/23/2016 12:34:17 PM | A | PASS |
|
|
Permit finaled
|
BLD16-01422
| FIRE-Final Inspection | 5/23/2016 | 5/23/2016 | 5/23/2016 11:04:13 AM | P | PASS |
|
|
Life safety passed
|
BLD16-01422
| FIRE-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 10:58:46 AM | A | FAIL |
|
|
Need to mount the new fire extinguisher and provide annual inspection.
|
NAF16-00025
| INSP-Final | 5/20/2016 | 5/23/2016 | 5/23/2016 10:45:08 AM | A | PASS |
|
|
Permit finaled
|
BLD16-01361
| FIRE-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 10:26:48 AM | A | FAIL |
|
|
All items have been corrected except the two new exit signs have no battery backup. Owner is going to replace. I rescheduled an inspection for tomorrow morning.
|
BLD14-02837
| FIRE-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 9:29:32 AM | A | PASS |
|
|
Phase 1 life safety passed.
|
FIR15-00822
| INSP-Sprinkler Rough-in/Hydro | 5/20/2016 | 5/23/2016 | 5/23/2016 9:04:06 AM | A | PASS |
|
|
Overhead hydro test passed.
|
FIR16-00274
| INSP-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 8:40:09 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00345
| INSP-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 8:36:07 AM | A | FAIL |
|
|
I tested the interconnect with the hood supression system and that reported to the facp. But there were no approved plans on site. Also per the contractor the two duct smoke detectors included on the scope of work have been deleted so prior to a final sign off I need as-builts to Lee and city approved plans to verify installation.
|
FIR16-00288
| INSP-Final Inspection | 5/20/2016 | 5/23/2016 | 5/23/2016 8:30:51 AM | A | FAIL |
|
|
Suppression system functioned but before a final sign off is given the Fire Dept needs to approve of the manual pull station location and I wll need to sign the final documents
|
FIR16-00316
| INSP-Sprinkler Rough-in/Hydro | 5/20/2016 | 5/23/2016 | 5/23/2016 7:26:50 AM | A | FAIL |
|
|
Inspection was just for two heads in hard lids but there were no approved plans on site. I also noted wood bracing above the future ceiling that is installed in a space with no upright sprinkler protection that will have to be addressed prior to a cover inspection.
|