BLD16-04520
| FIRE-Conference | 5/22/2017 | 5/23/2017 | 5/23/2017 11:47:16 AM | P | DONE |
|
|
I discussed exit door hardware with Vlad Phone #: ###-####
|
BLD17-01519
| FIRE-Final Inspection | 5/23/2017 | 5/23/2017 | 5/23/2017 11:46:26 AM | P | FAIL |
|
|
Provide sprinkler modifications for the overspaced pendants, provide single action hardware on one of the main exit doors, repair exit sign/emergency lights. Provide verification that the annual inspection for the fire sprinkler system is current. An upgrade agreement for the existing fire sprinkler system needs to be approved by the Boise Fire Dept prior to a sign off as per direction of the Assistant Chief Ron Johnson.
|
BLD17-01244
| FIRE-Final Inspection | 5/22/2017 | 5/23/2017 | 5/23/2017 8:37:16 AM | A | PASS |
|
|
life safety passed
|