Inspections for the day of: Tuesday, May 23, 2017.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04520 FIRE-Conference5/22/20175/23/20175/23/2017 11:47:16 AMPDONE
I discussed exit door hardware with Vlad Phone #: ###-####
BLD17-01519 FIRE-Final Inspection5/23/20175/23/20175/23/2017 11:46:26 AMPFAIL
Provide sprinkler modifications for the overspaced pendants, provide single action hardware on one of the main exit doors, repair exit sign/emergency lights. Provide verification that the annual inspection for the fire sprinkler system is current. An upgrade agreement for the existing fire sprinkler system needs to be approved by the Boise Fire Dept prior to a sign off as per direction of the Assistant Chief Ron Johnson.
BLD17-01244 FIRE-Final Inspection5/22/20175/23/20175/23/2017 8:37:16 AMAPASS
life safety passed