BLD17-04274
| FIRE-Conference | 5/23/2018 | 5/23/2018 | 5/23/2018 3:23:48 PM | P | DONE |
|
|
The project superintendant and I went over the door hardware requirements and exit path requirements.
|
FIR18-00129
| INSP-Sprinkler Rough-in | 5/22/2018 | 5/23/2018 | 5/23/2018 2:52:57 PM | P | PART |
|
|
Piping is ok to cover. I noted one pendant needs to be relocated near the front of the building and heads need to be added/relocated in two storage areas. I will check these heads at next inspection but piping can be covered.
Contact Andrew Larson - ###-#### 30 min prior to RTC Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD18-00213
| FIRE-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 2:30:06 PM | P | PASS |
|
|
life safety passsed
Please call 30-45min ahead for access - Jim Phone #: ###-####
|
BLD18-00019
| FIRE-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 2:28:47 PM | P | PASS |
|
|
Life safety passed
Please call 30-45min ahead for access - Jim Phone #: ###-####
|
FIR18-00292
| INSP-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 1:27:21 PM | P | PASS |
|
|
Permit finaled
please schedule for 1pm. thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR18-00296
| INSP-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 1:27:00 PM | P | PASS |
|
|
Permit finaled
please schedule for 1pm. thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR18-00286
| INSP-Sprinkler Rough-in | 5/22/2018 | 5/23/2018 | 5/23/2018 11:34:25 AM | A | PART |
|
|
Partial for depth of cover for the underground supply piping from the point of connection to the water meter. The piping is ok for cover. Still need from the water meter to the in building riser installed and inspected.
, call Anthony to coordinate. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00064
| INSP-Sprinkler Rough-in | 5/23/2018 | 5/23/2018 | 5/23/2018 11:30:43 AM | P | PASS |
|
|
Todays inspection was just for the drops from the existing branchlines. They all looked good. I noted that sprinkler coverage is missing under the overhead door and once the ceiling was installed under the door a combustible concealed space would be created that will require sprinkler protection.
Call Anthony to coordinate, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD17-02424
| FIRE-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 10:16:24 AM | A | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by David Scaggs
|
BLD18-01239
| FIRE-Final Inspection | 5/22/2018 | 5/23/2018 | 5/23/2018 10:00:41 AM | A | FAIL |
|
|
Need the exit sign at the rear exit fixed as previously requested.
requst early as poss // Suman Phone #: ###-####
|