Inspections for the day of: Friday, May 24, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00124 INSP-Sprinkler Rough-in5/23/20025/24/20025/24/2002 12:00:00 AMAFAIL
Hydro test failed, provide additional hanger on 3" main in south west corner of basement, provide sprinkler head in elevator shaft (per plan), provide retaining straps on all top beam clamps in basement, additional sprinkler heads may be required in spaces and the top and bottom of the east stairs, secure insulation to deck, provide earthquake bracing were all thread rod exceeds 6" in length, resubmitt plans that show the feed main changes to the second floor system 5/24/2002 10:47:56 AM
BLD02-00839 FIRE-Final Inspection5/23/20025/24/20025/24/2002 12:00:00 AMPPASS
Fire life/safety finaled. No card was available to sign 5/24/2002 12:25:06 PM
BLD02-00727 FIRE-Final Inspection5/24/20025/24/20025/24/2002 12:00:00 AMPFAIL
repair exit signs, provide emergency lights, provide a K class and an ABC fire extinguishers, remove the key hardware from one of the main exit doors and replace with approved hardware, remove the thumbturn and the door knob on the rear door (replace knob with lever), change all door hardware to match General notes A-D, test fire alarm system, provide address 5/24/2002 4:57:52 PM