FIR03-00315
| INSP-Final Inspection | 5/18/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | FAIL |
|
|
Clifford; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Trouble on NAC-1 circuit - 2; descriptor for NAC/EVAC trouble modules; water flow restores alarm when flow stops 5/24/2004 10:32:22 AM
|
FIR04-00155
| INSP-Alarm Testing | 5/20/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Cliff Miller outside sprinkler bell not working with dry flow; change descriptors to indicate dry and wet sprinkler flow zones; need maps; need to test all duct detectors; need record of completion 5/24/2004 4:33:47 PM
|
FIR03-00192
| INSP-Final Inspection | 5/21/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | PASS |
|
|
Contact: Jim; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR04-00246
| INSP-Final Inspection | 5/21/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/21/2004 at 11:27:29 AM. Contact: ###-####.
|
BLD03-02893
| FIRE-Final Inspection | 5/21/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/21/2004 at 11:28:54 AM. Contact: ###-####.
|
FIR04-00118
| INSP-Final Inspection | 5/21/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
|
FIR03-00598
| INSP-Sprinkler Rough-in/Hydro | 5/24/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 5/24/2004 at 10:24:34 AM. Contact: ###-####. Hydro on overhead and FDC okay 5/24/2004 2:31:19 PM
|
FIR03-00752
| INSP-Final Inspection | 5/24/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | P | PASS |
|
|
|
BLD04-00031
| FIRE-Conference | 5/24/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | P | PART |
|
|
Met with Rick about items for final: need to test all emergency/exit signs for battery back-up; remove deadbolts from exit doors; provide occupant load sign; install fire extinguishers 5/24/2004 4:35:25 PM
|
FIR04-00141
| INSP-Sprinkler Rough-in/Hydro | 5/21/2004 | 5/24/2004 | 5/24/2004 12:00:00 AM | P | FAIL |
|
|
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley remove tape from all heads; need spare heads; need blue annual inspection tag; install escutcheons/canopies; need overhead and underground certificates; outside bell not working with dry sprinkler flow 5/24/2004 4:32:02 PM
|