Inspections for the day of: Monday, May 24, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00315 INSP-Final Inspection5/18/20045/24/20045/24/2004 12:00:00 AMAFAIL
Clifford; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Trouble on NAC-1 circuit - 2; descriptor for NAC/EVAC trouble modules; water flow restores alarm when flow stops 5/24/2004 10:32:22 AM
FIR04-00155 INSP-Alarm Testing5/20/20045/24/20045/24/2004 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Cliff Miller outside sprinkler bell not working with dry flow; change descriptors to indicate dry and wet sprinkler flow zones; need maps; need to test all duct detectors; need record of completion 5/24/2004 4:33:47 PM
FIR03-00192 INSP-Final Inspection5/21/20045/24/20045/24/2004 12:00:00 AMAPASS
Contact: Jim; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
FIR04-00246 INSP-Final Inspection5/21/20045/24/20045/24/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/21/2004 at 11:27:29 AM. Contact: ###-####.
BLD03-02893 FIRE-Final Inspection5/21/20045/24/20045/24/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/21/2004 at 11:28:54 AM. Contact: ###-####.
FIR04-00118 INSP-Final Inspection5/21/20045/24/20045/24/2004 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
FIR03-00598 INSP-Sprinkler Rough-in/Hydro5/24/20045/24/20045/24/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 5/24/2004 at 10:24:34 AM. Contact: ###-####. Hydro on overhead and FDC okay 5/24/2004 2:31:19 PM
FIR03-00752 INSP-Final Inspection5/24/20045/24/20045/24/2004 12:00:00 AMPPASS
BLD04-00031 FIRE-Conference5/24/20045/24/20045/24/2004 12:00:00 AMPPART
Met with Rick about items for final: need to test all emergency/exit signs for battery back-up; remove deadbolts from exit doors; provide occupant load sign; install fire extinguishers 5/24/2004 4:35:25 PM
FIR04-00141 INSP-Sprinkler Rough-in/Hydro5/21/20045/24/20045/24/2004 12:00:00 AMPFAIL
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley remove tape from all heads; need spare heads; need blue annual inspection tag; install escutcheons/canopies; need overhead and underground certificates; outside bell not working with dry sprinkler flow 5/24/2004 4:32:02 PM