ELE05-00140
| ELE-Aging Inspection | 5/24/2005 | 5/24/2005 | 5/24/2005 3:08:58 PM | | PEND |
|
|
wsuc
|
ELE05-01729
| Final | 5/23/2005 | 5/24/2005 | 5/24/2005 3:08:01 PM | P | NR |
|
|
A final inspection is needed for mid afternoon at 3:30 for rooftop access. Electrician’s cell: ###-#### (Steve) Thank you!; Phone #: ###-#### no one at site called contractor
|
ELE05-01522
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 2:40:23 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
|
ELE05-01819
| Temporary Service | 5/24/2005 | 5/24/2005 | 5/24/2005 2:17:23 PM | P | PASS |
|
|
steve ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie t/s o/h new ok
|
ELE05-00140
| Temporary Service | 5/24/2005 | 5/24/2005 | 5/24/2005 2:06:43 PM | P | CANC |
|
|
|
ELE05-01787
| Temporary Service | 5/24/2005 | 5/24/2005 | 5/24/2005 1:54:20 PM | P | PASS |
|
|
Jack sorry that temp pole was brand new and should of had a GFI breaker. lets try this again. call francis with any questions 573.7484; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa t/s o/h new ok
|
ELE04-03437
| Final | 5/20/2005 | 5/24/2005 | 5/24/2005 1:35:22 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen needs to talk to contractor about listings called left message
|
ELE05-00876
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 12:46:47 PM | P | FAIL |
|
|
andy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called 210.52 needs outlet right of sink for counter space on pen. counter, also install appliance garage or outlets for required spacing for countertops, 406.8 all out
|
ELE05-01787
| Temporary Service | 5/23/2005 | 5/24/2005 | 5/24/2005 11:44:56 AM | A | FAIL |
|
|
francis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called needs gfci for 220 v recept
|
ELE05-01251
| Final | 5/23/2005 | 5/24/2005 | 5/24/2005 10:26:19 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/23/2005 at 10:23:53 PM. Contact: ###-####. ok card signed
|
ELE05-01812
| Final | 5/23/2005 | 5/24/2005 | 5/24/2005 10:14:36 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok
|
ELE05-01783
| Final | 5/23/2005 | 5/24/2005 | 5/24/2005 9:48:55 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/23/2005 at 12:00:19 PM. Contact: ###-####. cor. posted called 250.52&104 (A)(1) grd or bond water system at service, 250.142(B) shall provide insulated neutral from p/s to subpanel, 4wire circuit to rang
|
ELE05-01078
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 8:55:32 AM | A | PASS |
|
|
BILL - ###-#### Internet Inspection Request from: Bob Glenn ok
|
ELE05-00069
| ELE-Aging Inspection | 5/24/2005 | 5/24/2005 | 5/24/2005 8:33:52 AM | | PASS |
|
|
|
ELE04-01980
| Final | 5/23/2005 | 5/24/2005 | 5/24/2005 8:27:29 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/23/2005 at 12:37:02 PM. Contact: ###-####. ok no card corrections made
|
ELE05-00123
| ELE-Aging Inspection | 5/24/2005 | 5/24/2005 | 5/24/2005 7:55:23 AM | | PASS |
|
|
|
ELE05-00123
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 12:00:00 AM | A | PASS |
|
|
ok
|
ELE05-01002
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 12:00:00 AM | P | PASS |
|
|
|
ELE05-00069
| Final | 5/24/2005 | 5/24/2005 | 5/24/2005 12:00:00 AM | P | PASS |
|
|
|
ELE05-01344
| Electrical Rough-In | 5/23/2005 | 5/24/2005 | 5/23/2005 3:34:18 PM | A | PASS |
|
|
per your request ceiling r/i ok
|