Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC05-01650 Pressure Test5/23/20055/24/20055/24/2005 3:44:22 PMPPASS
Please inspect as close to 4:00p.m. as possible. Call with any problems. Thanks, April.; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
MEC05-01650 Final5/23/20055/24/20055/24/2005 3:44:13 PMPPASS
Please inspect as close to 4:00p.m. as possible. Call with any problems. Thanks, April.; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
MEC05-01586 Pressure Test5/24/20055/24/20055/24/2005 3:39:11 PMPPASS
please call 30 min. before for access.; Phone #: ###-#### Internet Inspection Request from: Stacy Ware
MEC05-01586 Final5/24/20055/24/20055/24/2005 3:39:03 PMPPASS
please call 30 min. before for access.; Phone #: ###-#### Internet Inspection Request from: Stacy Ware
MEC05-01101 Final5/23/20055/24/20055/24/2005 3:38:51 PMPPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
MEC05-01663 Rough-in5/23/20055/24/20055/24/2005 2:29:03 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rick Stockman
MEC05-01648 Rough-in5/24/20055/24/20055/24/2005 2:18:45 PMPPASS
###-#### cheryl
MEC05-01647 Rough-in5/24/20055/24/20055/24/2005 2:18:29 PMPFAIL
Scheduled by a contractor via Hello! on 5/24/2005 at 8:07:18 AM. Contact: ###-####. maintain 1" clearance at fire stop
MEC05-01368 Rough-in5/23/20055/24/20055/24/2005 2:03:08 PMPFAIL
this is 25/1 not 26/1; Phone #: ###-#### Internet Inspection Request from: Rick Stockman can not find this address, found 991 then 1065
MEC05-01656 Rough-in5/23/20055/24/20055/24/2005 1:56:36 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen support flex above grid and insulate metal duct above grid but below insulation at attic
MEC05-01177 Rough-in5/23/20055/24/20055/24/2005 1:13:08 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Sorensen need to remove vent limitor at mp gas regulator on roof and add elbow and piece of pipe to gasline so gas line isn't under strain
MEC04-03476 DOC - Permit Expired5/24/20055/24/20055/24/2005 11:53:34 AMPPASS
MEC04-03326 Extend Permit 180 days5/23/20055/24/20055/24/2005 11:49:13 AMACANC
Permit due to expire 5/22/05. Req to extend. THANKS!; Phone #: ###-#### Internet Inspection Request from: DeAnna Barrett
MEC05-00764 Final5/23/20055/24/20055/24/2005 9:56:49 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2005 at 1:48:21 PM. Contact: ###-####.
MEC05-00912 Final5/23/20055/24/20055/24/2005 9:37:49 AMAPASS
james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
MEC05-01576 Pressure Test5/23/20055/24/20055/24/2005 9:24:37 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2005 at 12:20:07 PM. Contact: ###-####.
MEC05-01576 Rough-in5/23/20055/24/20055/24/2005 9:24:10 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2005 at 12:19:51 PM. Contact: ###-####.
MEC05-01030 Final5/23/20055/24/20055/24/2005 9:08:03 AMAPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
MEC04-03476 MEC-Aging Inspection5/24/20055/24/20055/24/2005 8:51:01 AM FAIL