Inspections for the day of: Tuesday, May 24, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01745 Electrical Rough-In5/24/20055/24/20055/24/2005 4:47:51 PMPCANC
Scheduled by a contractor via Hello! on 5/24/2005 at 7:57:35 AM. Contact: ###-####. they called and need to delay for a day
ELE05-00416 Final5/24/20055/24/20055/24/2005 3:50:33 PMPCANC
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore owner called and wasn't ready
ELE05-01816 Electrical Rough-In5/24/20055/24/20055/24/2005 2:25:05 PMPPASS
Rough in inspection for bathrooms; Phone #: ###-#### Internet Inspection Request from: Joe Thomas bathrooms only ric ok
ELE05-00284 Electrical Rough-In5/24/20055/24/20055/24/2005 1:57:25 PMPPASS
PLEASE CONTACT STEVE, THANK YOU.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters soffits for building and parking lot perimeter u/g ok
ELE05-01799 Temporary Service5/24/20055/24/20055/24/2005 1:27:37 PMPPASS
dan =re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie t/s u/g n ok
ELE05-01800 Rough-In Permanent Service5/24/20055/24/20055/24/2005 12:59:08 PMPPASS
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, ric ok, p/s u/g n ok
ELE05-01820 Electrical Rough-In5/24/20055/24/20055/24/2005 12:45:24 PMPPASS
###-#### - mike called contr, left survey, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, BCC all make-up to be done, recpt on N side garage, job id sticker shall be posted
ELE05-00056 Final5/23/20055/24/20055/24/2005 10:35:40 AMAFAIL
###-#### - mike 422.31(B) breaker lo for dishwasher, 422.16 cord for disposal shall be installed, 314.20 flush recpt under sink, 210.52(E) gfci rcpt shall be installed at back of house
ELE05-01675 Final5/23/20055/24/20055/24/2005 10:11:18 AMANH
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr and told him to arrange doors to be open. work was for track lite and dimmer switch at stage area, per Matt.
ELE05-01569 Final5/23/20055/24/20055/24/2005 10:09:27 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles correction made. ok to final
ELE05-01785 Electrical Rough-In5/23/20055/24/20055/24/2005 9:48:27 AMAPASS
Scheduled by a contractor via Hello! on 5/23/2005 at 2:44:30 PM. Contact: ###-####. ok to cver west wall. corrections made
ELE05-01468 Final5/23/20055/24/20055/24/2005 8:27:06 AMAFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 680.22(A)(2) recpts shall be not less than 10 ft from inside edge of pool, 680.22(B)(2) fixtures over pool shall be totally enclosed and min 5 ft horizontal from edge of pool
ELE05-00993 Final5/24/20055/24/20055/24/2005 8:23:52 AMAPASS
Scheduled by a contractor via Hello! on 5/24/2005 at 6:32:36 AM. Contact: ###-####. called contr to hook up a/c ok to final
ELE05-01340 Permanent Service5/23/20055/24/20055/23/2005 4:25:10 PMAPASS
tom ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s u/g n ok