BLD06-00147
| FIRE-Final Inspection | 5/24/2006 | 5/24/2006 | 5/25/2006 10:37:33 AM | P | FAIL |
|
|
Need to provide approved hardware at the back exit door and remove the thumbturn and grate with padlock. The fire sprinkler work in the tenant space will require inspection and approval prior to occupancy.
|
BLD05-03484
| FIRE-Final Inspection | 5/24/2006 | 5/24/2006 | 5/24/2006 4:10:30 PM | P | PASS |
|
|
Occupant sensors have been installed as required and tested for functionality, inspection passed.
|
BLD01-02245
| FIRE-Final Inspection | 5/18/2006 | 5/24/2006 | 5/24/2006 3:41:44 PM | A | PASS |
|
|
Items on correction notice have been completed, fire life safety is acceptable.
|
FIR06-00320
| INSP-Sprinkler Rough-in/Hydro | 5/23/2006 | 5/24/2006 | 5/24/2006 3:40:43 PM | P | PART |
|
|
Overhead fire sprinkler is approved for cover.
|
FIR06-00281
| INSP-Sprinkler Rough-in | 5/23/2006 | 5/24/2006 | 5/24/2006 1:25:15 PM | A | FAIL |
|
|
One head in the basement as circled on approved plans requires vertical restraint, the 5' section of 11/4 pipe as circled on plans exceeds allowable deflection distances, need to provide cold cavity protection above the dining area, one head has been added in the second floor bathroom, some areas as piped do not match routing as shown on stamped plans.
|
FIR06-00128
| INSP-Sprinkler Rough-in/Hydro | 5/23/2006 | 5/24/2006 | 5/24/2006 12:36:47 PM | P | NR |
|
|
Not ready for inspection per phone call from contractor.
|
FIR05-00257
| INSP-Final Inspection | 5/23/2006 | 5/24/2006 | 5/24/2006 12:34:53 PM | A | PASS |
|
|
The remainder of fire alarm work for this permit passed inspection, fire alarm finaled.
|
BLD06-00401
| FIRE-Final Inspection | 5/24/2006 | 5/24/2006 | 5/24/2006 11:54:25 AM | A | FAIL |
|
|
Three locations are missing emergency lights for the path of egress, need to provide and install fire extinguishers as discussed, provide suite address, doors are not installed at this time for verification of hardware requirements.
|
FIR05-00421
| FIR-Aging Inspection | 5/24/2006 | 5/24/2006 | 5/24/2006 10:12:21 AM | | DONE |
|
|
Project not complete, wip.
|
FIR06-00293
| INSP-Sprinkler Rough-in/Hydro | 5/22/2006 | 5/24/2006 | 5/23/2006 9:49:03 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|