Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00795 INSP-Supply line flush5/24/20065/24/20065/24/2006 4:38:35 PMPPASS
Underground flush passed.
FIR05-00788 INSP-Supply line flush5/24/20065/24/20065/24/2006 4:38:14 PMPPASS
Underground flush passed.
FIR05-00795 INSP-Sprinkler Rough-in/Hydro5/24/20065/24/20065/24/2006 4:37:44 PMPPASS
Underground supply hydro test passed.
FIR05-00788 INSP-Sprinkler Rough-in/Hydro5/24/20065/24/20065/24/2006 3:09:59 PMPPASS
Underground supply hydro test passed.
BLD06-00600 FIRE-Final Inspection5/24/20065/24/20065/24/2006 2:00:08 PMPPART
I gave a temporary occupancy until I can find out from Sam or Mary if fire alarm modifications are required
BLD06-00142 FIRE-Final Inspection5/24/20065/24/20065/24/2006 1:55:16 PMPPASS
Life safety finaled
BLD06-00250 FIRE-Final Inspection5/23/20065/24/20065/24/2006 12:39:12 PMAFAIL
Life safety is ok to final when the fire alarm permit is finaled.
BLD05-01694 FIRE-Final Inspection5/23/20065/24/20065/24/2006 12:38:17 PMAFAIL
The insulation has not been fixed yet and there are two sheets of plywood in the rear of the store that are over 4' wide that need sprinkler coverage under.
FIR06-00166 INSP-Final Inspection5/23/20065/24/20065/24/2006 10:18:39 AMAFAIL
Provide correct sample tube for the duct detector and change descruption of duct detector location.
FIR06-00196 INSP-Final Inspection5/23/20065/24/20065/24/2006 10:15:57 AMAFAIL
Can't final until the ceiling tile is installed. Sprinkler piping is ok to cover.
FIR05-00856 INSP-Final Inspection5/23/20065/24/20065/24/2006 8:11:37 AMAPASS
Permit finaled