Inspections for the day of: Thursday, May 24, 2007.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00314 FIRE-Final Inspection5/24/20075/24/20075/25/2007 1:39:45 PMPPASS
Vanilla shell fire life safety inspection passed.
FIR07-00061 INSP-Final Inspection5/23/20075/24/20075/25/2007 12:25:11 PMAPASS
Fire sprinkler final inspection passed, permit finaled.
FIR06-00988 INSP-Sprinkler Rough-in5/23/20075/24/20075/24/2007 4:20:08 PMPPART
UG fire supply line install matches approved plans-okay to bury, also inspected three rooms with hard lid ceilings as circled and initialed on stamped plans okay for cover.
FIR07-00227 INSP-Final Inspection5/23/20075/24/20075/24/2007 3:58:45 PMPCANC
No time available to complete inspection request.
FIR07-00228 INSP-Final Inspection5/23/20075/24/20075/24/2007 3:58:14 PMPCANC
No time available to complete inspection.
FIR06-01017 INSP-Final Inspection5/23/20075/24/20075/24/2007 3:56:32 PMPFAIL
See comments per inspection completed by M. Timmerman.
FIR07-00454 INSP-Final Inspection5/23/20075/24/20075/24/2007 3:55:31 PMAPASS
The hood suppression system operated correctly under test conditions, noted the stock pot burner to be elevated within 4' of the hood edge as discussed-to be verified at BLD final.
BLD06-01488 FIRE-Final Inspection5/23/20075/24/20075/24/2007 2:46:03 PMADEFR
please call prior to going out there Todd ###-####...........Contractor to reschedule per conversation.
BLD06-00147 FIRE-Final Inspection5/23/20075/24/20075/24/2007 2:44:54 PMADEFR
Contractor to reschedule as discussed.
BLD06-03080 FIRE-Final Inspection5/24/20075/24/20075/24/2007 2:40:44 PMPPASS
Life safety finaled.
BLD06-01669 FIRE-Final Inspection5/24/20075/24/20075/24/2007 2:34:04 PMPPASS
Shell life safety finaled.
BLD07-00335 FIRE-Final Inspection5/23/20075/24/20075/24/2007 2:32:01 PMAPASS
Noted correction items are complete, door hardware at the restroom doors to be changed to fail safe single motion prior to structural final.
FIR06-00153 INSP-Final Inspection5/23/20075/24/20075/24/2007 2:09:30 PMPPASS
Per field inspection by M. Timmerman, fire alarm work passed inspection, permit finaled.
FIR05-00822 INSP-Final Inspection5/23/20075/24/20075/24/2007 2:07:40 PMAPART
Per field inspection by M. Timmerman, need verification of the dry system capacity prior to final acceptance.
BLD05-02429 FIRE-Final Inspection5/23/20075/24/20075/24/2007 12:48:25 PMAFAIL
Per field inspection by M. Timmerman need to remove the manual thumbturn at the back exit door, provide current certification tag for the PFE, provide approved building address numbers.
FIR07-00352 INSP-Sprinkler Rough-in/Hydro5/22/20075/24/20075/24/2007 12:25:03 PMAPART
FS approved for cover at the hard lid ceilings.
FIR07-00397 INSP-Sprinkler Rough-in/Hydro5/22/20075/24/20075/24/2007 12:23:58 PMAFAIL
Upright sprinklers at some locations are installed beyond the max. allowable height below the deck, noted ceilings are okay to cover, can verifiy corrections at existing access hatch.
FIR07-00393 INSP-Sprinkler Rough-in/Hydro5/22/20075/24/20075/24/2007 12:21:40 PMAFAIL
Upright sprinklers are blocked by a full height partition above the ceiling.
FIR07-00430 INSP-Sprinkler Rough-in/Hydro5/23/20075/24/20075/24/2007 10:44:30 AMAPART
UG fire supply line is approved for bury to the point of connection at the property line.
FIR07-00300 INSP-Sprinkler Rough-in/Hydro5/23/20075/24/20075/24/2007 10:10:12 AMAPART
OH FS is okay for cover, noted sprinklers adjacent to the wall mounted soffit must be in compliance with NFPA 13 fig. 8.6.5.1.2(b).
FIR07-00294 INSP-Sprinkler Rough-in5/23/20075/24/20075/24/2007 10:04:22 AMAPART
OH fire sprinkler install is approved for cover at the sheetrock lid ceilings, noted no cover is allowed prior to rough-in inspection.
FIR07-00293 INSP-Sprinkler Rough-in5/23/20075/24/20075/24/2007 10:01:54 AMAPART
OH rough-in is acceptable for cover at the hard lid ceiling areas.
FIR06-00800 INSP-Sprinkler Rough-in/Hydro5/23/20075/24/20075/24/2007 9:33:25 AMAPART
24 hour air testing of the dry system passed.
FIR07-00225 INSP-Final Inspection5/23/20075/24/20075/24/2007 8:34:27 AMAPASS
Fire sprinkler permit finaled.