BLD07-00314
| FIRE-Final Inspection | 5/24/2007 | 5/24/2007 | 5/25/2007 1:39:45 PM | P | PASS |
|
|
Vanilla shell fire life safety inspection passed.
|
FIR07-00061
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/25/2007 12:25:11 PM | A | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
FIR06-00988
| INSP-Sprinkler Rough-in | 5/23/2007 | 5/24/2007 | 5/24/2007 4:20:08 PM | P | PART |
|
|
UG fire supply line install matches approved plans-okay to bury, also inspected three rooms with hard lid ceilings as circled and initialed on stamped plans okay for cover.
|
FIR07-00227
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 3:58:45 PM | P | CANC |
|
|
No time available to complete inspection request.
|
FIR07-00228
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 3:58:14 PM | P | CANC |
|
|
No time available to complete inspection.
|
FIR06-01017
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 3:56:32 PM | P | FAIL |
|
|
See comments per inspection completed by M. Timmerman.
|
FIR07-00454
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 3:55:31 PM | A | PASS |
|
|
The hood suppression system operated correctly under test conditions, noted the stock pot burner to be elevated within 4' of the hood edge as discussed-to be verified at BLD final.
|
BLD06-01488
| FIRE-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 2:46:03 PM | A | DEFR |
|
|
please call prior to going out there Todd ###-####...........Contractor to reschedule per conversation.
|
BLD06-00147
| FIRE-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 2:44:54 PM | A | DEFR |
|
|
Contractor to reschedule as discussed.
|
BLD06-03080
| FIRE-Final Inspection | 5/24/2007 | 5/24/2007 | 5/24/2007 2:40:44 PM | P | PASS |
|
|
Life safety finaled.
|
BLD06-01669
| FIRE-Final Inspection | 5/24/2007 | 5/24/2007 | 5/24/2007 2:34:04 PM | P | PASS |
|
|
Shell life safety finaled.
|
BLD07-00335
| FIRE-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 2:32:01 PM | A | PASS |
|
|
Noted correction items are complete, door hardware at the restroom doors to be changed to fail safe single motion prior to structural final.
|
FIR06-00153
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 2:09:30 PM | P | PASS |
|
|
Per field inspection by M. Timmerman, fire alarm work passed inspection, permit finaled.
|
FIR05-00822
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 2:07:40 PM | A | PART |
|
|
Per field inspection by M. Timmerman, need verification of the dry system capacity prior to final acceptance.
|
BLD05-02429
| FIRE-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 12:48:25 PM | A | FAIL |
|
|
Per field inspection by M. Timmerman need to remove the manual thumbturn at the back exit door, provide current certification tag for the PFE, provide approved building address numbers.
|
FIR07-00352
| INSP-Sprinkler Rough-in/Hydro | 5/22/2007 | 5/24/2007 | 5/24/2007 12:25:03 PM | A | PART |
|
|
FS approved for cover at the hard lid ceilings.
|
FIR07-00397
| INSP-Sprinkler Rough-in/Hydro | 5/22/2007 | 5/24/2007 | 5/24/2007 12:23:58 PM | A | FAIL |
|
|
Upright sprinklers at some locations are installed beyond the max. allowable height below the deck, noted ceilings are okay to cover, can verifiy corrections at existing access hatch.
|
FIR07-00393
| INSP-Sprinkler Rough-in/Hydro | 5/22/2007 | 5/24/2007 | 5/24/2007 12:21:40 PM | A | FAIL |
|
|
Upright sprinklers are blocked by a full height partition above the ceiling.
|
FIR07-00430
| INSP-Sprinkler Rough-in/Hydro | 5/23/2007 | 5/24/2007 | 5/24/2007 10:44:30 AM | A | PART |
|
|
UG fire supply line is approved for bury to the point of connection at the property line.
|
FIR07-00300
| INSP-Sprinkler Rough-in/Hydro | 5/23/2007 | 5/24/2007 | 5/24/2007 10:10:12 AM | A | PART |
|
|
OH FS is okay for cover, noted sprinklers adjacent to the wall mounted soffit must be in compliance with NFPA 13 fig. 8.6.5.1.2(b).
|
FIR07-00294
| INSP-Sprinkler Rough-in | 5/23/2007 | 5/24/2007 | 5/24/2007 10:04:22 AM | A | PART |
|
|
OH fire sprinkler install is approved for cover at the sheetrock lid ceilings, noted no cover is allowed prior to rough-in inspection.
|
FIR07-00293
| INSP-Sprinkler Rough-in | 5/23/2007 | 5/24/2007 | 5/24/2007 10:01:54 AM | A | PART |
|
|
OH rough-in is acceptable for cover at the hard lid ceiling areas.
|
FIR06-00800
| INSP-Sprinkler Rough-in/Hydro | 5/23/2007 | 5/24/2007 | 5/24/2007 9:33:25 AM | A | PART |
|
|
24 hour air testing of the dry system passed.
|
FIR07-00225
| INSP-Final Inspection | 5/23/2007 | 5/24/2007 | 5/24/2007 8:34:27 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|