BLD08-00264
| FIRE-Final Inspection | 5/18/2010 | 5/18/2010 | | P | |
|
|
Jim phone #: ###-####
|
FIR10-00187
| INSP-Final Inspection | 5/21/2010 | 5/24/2010 | 5/25/2010 10:43:03 AM | A | PART |
|
|
Overhead modifications are okay for cover at the drop ceilings in the TI areas.
|
FIR10-00061
| INSP-Final Inspection | 5/17/2010 | 5/24/2010 | 5/25/2010 10:41:34 AM | A | FAIL |
|
|
Correction items for areas inspected to date include; HVAC duct smoke detector at address L2-S29 in concessions room 210 "Perch" failed to initiate unit shut down- plan sheet F.A.2.1, duct smoke detector address L1-S29 in "Tators" failed to shut down HVAC unit, missing tamper switch and monitor module at the outside control valve for the fire sprinkler system- F.A. 2.3/2.0, missing one notification appliance at exhibit hall 200- sheet F.A.2.5, post signage at the door to the FACP room per review notes, notification devices have been changed from wall mount to ceiling mount at the restrooms F.A.2.5, incorrect cd setting at lockers 179, minor adjustments to as-built plans discussed, need clarification of room use at the "business center" area D as is lacking notification. Items inspected include kitchen hood monitoring, fire sprinkler riser supervision, heat detectors, manual pull station, area smoke detection at the basement, all duct detectors, door holds, walkthrough regarding notification appliance locations for areas A, C and D.
|
BLD10-00730
| FIRE-Final Inspection | 5/21/2010 | 5/24/2010 | 5/24/2010 10:43:42 AM | A | PASS |
|
|
Fire life safety inspection passed.
|