Inspections for the day of: Monday, May 24, 2010.
Number of inspections: 4
Percentage of inspections complete: 75 %
Percentage of inspections not complete: 25 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00264 FIRE-Final Inspection5/18/20105/18/2010 P 
Jim phone #: ###-####
FIR10-00187 INSP-Final Inspection5/21/20105/24/20105/25/2010 10:43:03 AMAPART
Overhead modifications are okay for cover at the drop ceilings in the TI areas.
FIR10-00061 INSP-Final Inspection5/17/20105/24/20105/25/2010 10:41:34 AMAFAIL
Correction items for areas inspected to date include; HVAC duct smoke detector at address L2-S29 in concessions room 210 "Perch" failed to initiate unit shut down- plan sheet F.A.2.1, duct smoke detector address L1-S29 in "Tators" failed to shut down HVAC unit, missing tamper switch and monitor module at the outside control valve for the fire sprinkler system- F.A. 2.3/2.0, missing one notification appliance at exhibit hall 200- sheet F.A.2.5, post signage at the door to the FACP room per review notes, notification devices have been changed from wall mount to ceiling mount at the restrooms F.A.2.5, incorrect cd setting at lockers 179, minor adjustments to as-built plans discussed, need clarification of room use at the "business center" area D as is lacking notification. Items inspected include kitchen hood monitoring, fire sprinkler riser supervision, heat detectors, manual pull station, area smoke detection at the basement, all duct detectors, door holds, walkthrough regarding notification appliance locations for areas A, C and D.
BLD10-00730 FIRE-Final Inspection5/21/20105/24/20105/24/2010 10:43:42 AMAPASS
Fire life safety inspection passed.