FIR15-00791
| INSP-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 3:03:31 PM | P | PASS |
|
|
Permit finaled
|
BLD15-01869
| FIRE-Final Inspection | 5/20/2016 | 5/24/2016 | 5/24/2016 3:02:03 PM | P | CANC |
|
|
Clinton Phone #: ###-####
|
FIR15-00822
| INSP-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 3:01:44 PM | P | CANC |
|
|
Mark is the contact. Thanks. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR15-00887
| INSP-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 3:00:39 PM | P | CANC |
|
|
Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price
|
FIR16-00335
| INSP-Supply line flush | 5/23/2016 | 5/24/2016 | 5/24/2016 3:00:04 PM | P | PASS |
|
|
Underground flush for all six lines passed
|
BLD16-00427
| FIRE-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 12:37:59 PM | P | FAIL |
|
|
Provide permit for the newly installed hood suppression system, the hood suppression system manual pull station is located too close to the hood, provide exit signs/emergency lights as per the approved plans, provide sticker at the main exit door and indicator for the lock, provide panic hardware for door 105, provide lever hardware and remove the deadbolt on door 107C, provide occupant load sign, provide "K" class fire extinguisher.
|
NAF16-00037
| INSP-Final | 5/23/2016 | 5/24/2016 | 5/24/2016 12:35:09 PM | P | PASS |
|
|
Permit finaled
|
NAF16-00004
| INSP-Final | 5/23/2016 | 5/24/2016 | 5/24/2016 12:34:05 PM | A | PASS |
|
|
Life safety passed. Hardware changed at the office/warehouse door.
|
BLD16-00927
| FIRE-Final Inspection | 5/17/2016 | 5/24/2016 | 5/24/2016 11:44:12 AM | P | FAIL |
|
|
Provide permit as original request for the hood suppression system and repair the exit signs.
|
BLD16-01361
| FIRE-Final Inspection | 5/23/2016 | 5/24/2016 | 5/24/2016 9:59:41 AM | A | PASS |
|
|
Life safety passed
|
FIR16-00333
| INSP-Sprinkler Rough-in | 5/23/2016 | 5/24/2016 | 5/24/2016 8:44:15 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered
|