Inspections for the day of: Friday, May 24, 2019.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03204 Final5/23/20195/24/20195/24/2019 2:23:33 PMPFAIL
Any questions please call Louis at ###-####9 Phone #: ###-#### Inspection requested via web by Louis Keller 680.22A1 Receps shall not be located within 6ft of pool edge. (post recep in yard 5ft away)
ELE19-01873 Final5/23/20195/24/20195/24/2019 2:20:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Tricia Henderson Final ok
ELE19-01716 Final5/24/20195/24/20195/24/2019 1:33:31 PMPPASS
tennant will be home. Phone #: ###-#### Inspection requested via web by Justin Yount Washer/ dryer circuits only final ok
ELE17-03393 Electrical Rough-In5/22/20195/24/20195/24/2019 1:19:47 PMPPASS
Contact: Caleb Burke... ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Training room ceiling only ok to cover
ELE19-00747 Final5/24/20195/24/20195/24/2019 1:11:02 PMPPART
Reinspection of Unit 137 for missing 2gang plate. Phone #: ###-#### Inspection requested via web by Tod Lane Correction made 137 final ok
ELE19-01884 Electrical Rough-In5/23/20195/24/20195/24/2019 12:21:49 PMPFAIL
Phone #: ###-#### Inspection requested via web by Craig Korell 210.11C3 Bath receps shall be 20A. (need to add 20A circuit for master vanity)
ELE19-01357 Final5/24/20195/24/20195/24/2019 12:05:21 PMPPASS
Call Jason with any questions at ###-####
Someone will be there Phone #: ###-#### Inspection requested via web by Clayton Morgan final ok
ELE15-03174 Final5/21/20195/24/20195/24/2019 11:57:08 AMAPASS
Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
ELE19-00481 Final5/24/20195/24/20195/24/2019 11:36:44 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE19-01770 Rough-In Permanent Service5/23/20195/24/20195/24/2019 11:18:23 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe rough in ok p/s u/g n ok
ELE19-01914 Electrical Rough-In5/23/20195/24/20195/24/2019 11:08:02 AMAPASS
Listing inspection for solar equipment;
It''s the first day for installing the solar panels, so all equipment is down and available; the inverters and empty raceway is exterior and ready to be inspected; thanks guys
Phone #: ###-#### Inspection requested via web by Ryan King listing only ok
ELE19-00192 Electrical Rough-In5/23/20195/24/20195/24/2019 10:37:13 AMAPASS
Duke is electrician on site - need cover for heated floor covering
Phone #: ###-#### Inspection requested via web by Matthew White Floor heat only ok to cover
ELE19-01923 Conference5/24/20195/24/20195/24/2019 10:02:09 AMPPASS
Jim Phone #: ###-#### This is a permit to correct corrections under ele19-00687. Kitchen was not under contractors scope of work. Met with owner to discuss kitchen counter requirments. Kitchen counter layout was changed from original design. 12 counter to right of range needs recep and counter to left of sink needs recep within 24in of end of cabinet. Informed owner mounting recep to bottom of upper cabinet is ok
ELE19-00687 Final5/23/20195/24/20195/24/2019 9:56:31 AMAPASS
Jim Phone #: ###-#### Kitchen counter correction will be made under ELE19-01923 Final ok
ELE18-04297 Final5/24/20195/24/20195/24/2019 9:51:47 AMAPASS
Key should be under a block Phone #: ###-#### Inspection requested via web by Neal Rumsey Corrections made final ok
ELE19-01921 Electrical Rough-In5/23/20195/24/20195/24/2019 9:35:52 AMAPASS
Please inspect the underground only for the new service.

Please call when you are on the way. Phone #: ###-#### Inspection requested via web by Spencer McLean Service is for a cell tower on property. Underground from service to Building ok to cover
ELE19-00923 Final5/23/20195/24/20195/24/2019 9:23:06 AMAPASS
Key in outlet at front door Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
ELE19-00922 Final5/23/20195/24/20195/24/2019 9:22:42 AMAPASS
Key in outlet at front door Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
ELE19-00747 Final5/22/20195/24/20195/24/2019 8:50:57 AMAPART
Final inspection on Units 137, 139, 238, 239. Phone #: ###-#### Inspection requested via web by Tod Lane 314.25. All boxes shall have cover plates. (137 missing 2gang cover in Shower room.) 139,238,239 Final ok