Inspections for the day of: Thursday, May 25, 2000.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-00186 FIRE-Final Inspection5/24/20005/25/20005/25/2000 12:00:00 AMAFAIL
Brad ###-#### Duct detectors for AHU; door hardware 5/25/00 1:41:23 PM
BLD99-03673 FIRE-Supply Line Flush5/24/20005/25/20005/25/2000 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 05/24/2000 at 13:20:04. Contact: ###-####. Need permit underground; not coated per NFPA 2Y 5/25/00 1:41:44 PM
FIR00-00275 INSP-Sprinkler Rough-in5/24/20005/25/20005/25/2000 12:00:00 AMAFAIL
underground Nat ###-#### Need thermal protection for underground main due to depth of bury at 2.5 ft. 5/25/00 1:42:09 PM
FIR99-00607 INSP-Sprinkler Rough-in/Hydro5/25/20005/25/20005/25/2000 12:00:00 AMPPASS
Ann ###-#### Ok to cover 5/26/00 1:30:43 PM
BLD98-02492 FIRE-Final Inspection5/25/20005/25/20005/25/2000 12:00:00 AMPPASS
BLD99-03400 FIRE-Final Inspection5/25/20005/25/20005/25/2000 12:00:00 AMPFAIL
panic on A3 room doors; alarm issues; c/n issued
FIR99-00668 INSP-Final Inspection5/25/20005/25/20005/25/2000 12:00:00 AMPPASS
FIR00-00076 INSP-Final Inspection5/25/20005/25/20005/25/2000 12:00:00 AMPPASS
FIR00-00009 INSP-Conference5/25/20005/25/20005/25/2000 12:00:00 AMPPART
met with Lynn about obstructed heads in main store; canopies over 4 ft require heads; sway bracing needed. c/n issued on 5/24 to general contractor about the above
FIR00-00318 INSP-Sprinkler Rough-in5/25/20005/25/20005/25/2000 12:00:00 AMPFAIL
supply line cover - not coated properly; fire sprinkler plan not permitted