Inspections for the day of: Tuesday, May 25, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-01160 Final5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
dan ; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 410.8 clearence closet fixture, 250.148 grd metal box in kit counter 5/25/2004 8:45:33 AM
ELE04-01159 Final5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
dan ; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 410.8 clearence closet fixture 5/25/2004 8:42:51 AM
ELE04-01278 Final5/24/20045/25/20045/25/2004 12:00:00 AMAPASS
Corrections made 5/24/04.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok 5/25/2004 9:59:05 AM
ELE04-01130 Final5/24/20045/25/20045/25/2004 12:00:00 AMAPASS
Victor; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 5/25/2004 8:58:16 AM
ELE04-01529 Final5/24/20045/25/20045/25/2004 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer see added p/s power was turned off ID power needed tag and electrical contractgor to look at service 5/25/2004 9:33:10 AM
ELE04-01529 Permanent Service5/25/20045/25/20045/25/2004 12:00:00 AMAPASS
p/s o/h rec. ok
ELE04-01131 Final5/25/20045/25/20045/25/2004 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Andy Rose cor. called shall terminate all bonds and GEC to p/s not sub panel, and isolate grds and neutrals at sub panel 5/25/2004 3:13:38 PM
ELE04-01548 Temporary Service5/25/20045/25/20045/25/2004 12:00:00 AMPPASS
###-#### Dan t/s u/g new ok 5/25/2004 11:49:26 AM
ELE04-01417 Final5/25/20045/25/20045/25/2004 12:00:00 AMPFAIL
PLEASE CALL MARK VAN GULICK WITH ANY QUESTIONS; Phone #: ###-#### Internet Inspection Request from: Jeff Radford cor 210.8 needs gfci for new recepts in kit. area called 5/25/2004 1:33:14 PM
ELE04-00695 Electrical Rough-In5/25/20045/25/20045/25/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 5/25/2004 at 8:07:38 AM. Contact: ###-####. cor. posted called 300.4,1 1/4", 314.43 no screws in plastic boxes, 300.14 short grds and splice shall be at 6", clearence for closet fixtures? 5/25/2004 2:22:54 PM
ELE04-00712 Electrical Rough-In5/24/20045/25/20045/25/2004 12:00:00 AMPPASS
bob; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls and ceiling ok 5/25/2004 12:49:27 PM