Inspections for the day of: Tuesday, May 25, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00567 FIRE-Final Inspection5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
Provide approved door hardware on the storage room and the furnace room doors and provide automatic closure on the store room door 5/25/2004 11:19:32 AM
BLD04-00568 FIRE-Final Inspection5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
Provide approved door hardware on the storage room and the furnace room doors and provide automatic closure on the store room door 5/25/2004 11:19:40 AM
BLD04-00569 FIRE-Final Inspection5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
Provide approved door hardware on the storage room and the furnace room doors and provide automatic closure on the store room door 5/25/2004 11:19:46 AM
BLD03-01575 FIRE-Final Inspection5/24/20045/25/20045/25/2004 12:00:00 AMAFAIL
Resubmit building plans showing as-built wall layout for the entire facility. Include correct room descriptions and locations of all rated walls, doors and glass. Room not shown on the plans in work area 157 has six bunk beds. Per on of the office personell this is used for overnight studies of insomnia. Provide description of this use and all other uses to the plan reviewer. Door hardware is not of approved type on some of the doors in the remodeled area and exit signs are not operating correctly. Atleast one sprinkler head is overspaced in the comference room. Pendant head in corridor outside of office 103 is too close to the wall (2") and a pendant head in storage room 134/135 exceeds 130 sq.ft. max. spacing. A full inspection will be conducted when revised plans are approved. 5/25/2004 11:25:48 AM
BLD04-00900 FIRE-Final Inspection5/25/20045/25/20045/25/2004 12:00:00 AMPPASS
Fire life safety finaled 5/25/2004 4:01:17 PM
BLD02-01157 FIRE-Final Inspection5/24/20045/25/20045/25/2004 12:00:00 AMPCANC
bob; Phone #: ###-#### Bob stated that the fire alarm contractor was not finished yet 5/25/2004 4:39:56 PM
FIR04-00155 INSP-Alarm Testing5/24/20045/25/20045/25/2004 12:00:00 AMPFAIL
Fire alarm was not ready due to missing makeup air unit and two thermoustats not wired and high and low voltage wire in the same conduit at dry pipe pressure switch. Sprinklers could not be finaled due to missing ceiling tile and canopies. Contractor needs to review fire dept. review notes prior to calling for inspection (fire extinguishers not ready nor was door hardware). All previous correction notices need to be verified for compliance. 5/25/2004 2:51:01 PM