Inspections for the day of: Wednesday, May 25, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00628 Final5/25/20055/25/20055/25/2005 1:57:45 PMPPART
Scheduled by a contractor via Hello! on 5/25/2005 at 10:34:31 AM. Contact: ###-####. ok card signed
ELE05-00622 Final5/25/20055/25/20055/25/2005 1:57:19 PMPPASS
Scheduled by a contractor via Hello! on 5/25/2005 at 10:33:16 AM. Contact: ###-####. ok card signed
ELE05-01532 Permanent Service5/25/20055/25/20055/25/2005 1:56:52 PMPPASS
Scheduled by a contractor via Hello! on 5/25/2005 at 7:53:03 AM. Contact: ###-####. p/s u/g new ok
ELE04-03671 Final5/25/20055/25/20055/25/2005 12:53:48 PMPPASS
Scheduled by a contractor via Hello! on 5/25/2005 at 9:27:44 AM. Contact: ###-####. no card
ELE05-00876 Final5/25/20055/25/20055/25/2005 12:18:34 PMPPASS
ANDY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
ok card signed
ELE05-00344 ELE-Aging Inspection5/25/20055/25/20055/25/2005 11:43:32 AM PART
called left message
ELE05-01406 Electrical Rough-In5/24/20055/25/20055/25/2005 10:00:42 AMAFAIL
underground for pool & potting--kelly ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
cor. posted called 680.10 needs 18" burial depth for u/g , 352.26 over 360 degrees of bends pvc
ELE05-00876 Final5/24/20055/25/20055/25/2005 9:34:05 AMAFAIL
ANDY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corrections not made called
ELE05-00307 Final5/24/20055/25/20055/25/2005 8:55:56 AMAFAIL
TONY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
cor met owner needs arc fualt for bedrms and correct wiring at gfci so they function properly
ELE04-03437 Final5/24/20055/25/20055/25/2005 8:14:12 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok no card
ELE05-00085 Final5/24/20055/25/20055/25/2005 7:55:42 AMAPASS
alan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok no card
ELE05-00579 ELE-Aging Inspection5/25/20055/25/20055/25/2005 7:14:18 AM PASS
ELE05-00579 Final5/25/20055/25/20055/25/2005 12:00:00 AMAPASS
ok