ELE05-00926
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/25/2005 4:24:22 PM | P | PASS |
|
|
Trench Cover inspection; Phone #: ###-#### Internet Inspection Request from: Celinda Winters u/g ok to cover for parking lot lighting
|
ELE05-00537
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/25/2005 4:20:39 PM | P | PASS |
|
|
Back office rough-in; Phone #: ###-#### Internet Inspection Request from: Celinda Winters told contr to repull one mc cable since he didn't have 6" free cond at box on west wall. ric walls only nw office
|
ELE05-01840
| Permanent Service | 5/25/2005 | 5/25/2005 | 5/25/2005 4:18:43 PM | P | NR |
|
|
chuck ###-#### called contr to wire feeders out of service
|
ELE05-01837
| Temporary Service | 5/25/2005 | 5/25/2005 | 5/25/2005 2:51:14 PM | P | FAIL |
|
|
###-#### rick called contr, left corr notice, fee due, 404.4 shall provide ckt directory, 408.38 panelboard shall have dead-front, 110.26(A)(1) work space depth shall be provided
|
ELE05-00056
| Final | 5/25/2005 | 5/25/2005 | 5/25/2005 1:59:04 PM | P | PASS |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
|
ELE05-01468
| Final | 5/25/2005 | 5/25/2005 | 5/25/2005 1:57:47 PM | P | NR |
|
|
Re-Final inspect on pool enclosure; Phone #: ###-#### Internet Inspection Request from: todd hall still needs to do jacuzzi area for abadoning lights too close to pool
|
ELE05-01774
| Electrical Rough-In | 5/25/2005 | 5/25/2005 | 5/25/2005 12:43:17 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/25/2005 at 7:37:19 AM. Contact: ###-####. see added insp for rip
|
ELE05-01450
| Final | 5/24/2005 | 5/25/2005 | 5/25/2005 10:14:09 AM | A | FAIL |
|
|
for temp occ ----tobi; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 110.26(A)(1) and (2) a/c disconnects shall have correct width and depth of working space, 110.3(B) listed equipment shall be installed in accordance with any ins
|
ELE04-03939
| Final | 5/24/2005 | 5/25/2005 | 5/25/2005 10:11:16 AM | A | PASS |
|
|
on the shell ----tobi; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final, signed card
|
ELE05-01015
| Final | 5/24/2005 | 5/25/2005 | 5/25/2005 10:10:12 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/24/2005 at 3:00:00 PM. Contact: ###-####. ok to final
|
ELE05-01801
| Temporary Service | 5/24/2005 | 5/25/2005 | 5/25/2005 9:55:42 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Bob Glenn t/s u/g n ok
|
ELE05-01630
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/25/2005 8:42:47 AM | A | PASS |
|
|
More Underslab; Phone #: ###-#### Internet Inspection Request from: Nikki Day middle section u/g ok to cover
|
ELE05-00235
| Final | 5/24/2005 | 5/25/2005 | 5/25/2005 8:12:10 AM | A | PASS |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-00236
| Final | 5/24/2005 | 5/25/2005 | 5/25/2005 8:11:31 AM | A | PASS |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr to change a/c breaker, ok to final
|
ELE05-01830
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/25/2005 8:08:42 AM | A | CANC |
|
|
underground conduit inspection please////###-#### mike u/g for now, for ipco, called contr, he didn't need city inspection yet
|
ELE05-01774
| Rough-In Permanent Service | 5/25/2005 | 5/25/2005 | 5/25/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2005 at 7:37:19 AM. Contact: ###-####. ric ok p/s u/g n ok
|
ELE05-00926
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/24/2005 3:49:08 PM | A | CANC |
|
|
Trench Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Celinda Winters Inspection cancelled from web by: Celinda Winters
|
ELE05-00537
| Electrical Rough-In | 5/24/2005 | 5/25/2005 | 5/24/2005 3:48:43 PM | A | CANC |
|
|
Back office rough-in; Phone #: ###-#### Internet Inspection Request from: Celinda Winters Inspection cancelled from web by: Celinda Winters
|