Inspections for the day of: Thursday, May 25, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01825 Temporary Service5/25/20065/25/20065/25/2006 4:58:34 PMPPASS
Scheduled by a contractor via Hello! on 5/25/2006 at 7:52:54 AM. Contact: ###-####. t/s o/h new ok
ELE06-00711 Electrical Rough-In5/24/20065/25/20065/25/2006 4:52:20 PMPPART
Scheduled by a contractor via Hello! on 5/24/2006 at 2:27:23 PM. Contact: ###-####. com rm basement, 3rms elevator lobby dir office 2nd floor anop
ELE06-01142 Final5/24/20065/25/20065/25/2006 2:19:38 PMAFAIL
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
corr. fee due posted called 680.26(B)(1) shall bond all parts of metal (cover track)314.3 shall follow manufactures instructions for plastic box with metallic raceway, 110.3 shall not remove sealing washer from listed R/T emt fittings
ELE06-01919 Electrical Rough-In5/25/20065/25/20065/25/2006 2:04:30 PMPPART
melissa bierman ###-#### conference only
ELE06-01778 Rough-In Permanent Service5/24/20065/25/20065/25/2006 12:18:58 PMAPASS
Internet Inspection Request from: Melyne Davis r/i p/s u/g new ok
ELE06-01899 Electrical Rough-In5/24/20065/25/20065/25/2006 10:42:55 AMAPASS
roger ###-#### walls ok no boxes shall be covered by wall finish called
ELE06-01892 Permanent Service5/24/20065/25/20065/25/2006 10:13:18 AMAPASS
pat - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec. ok
ELE06-01892 Final5/25/20065/25/20065/25/2006 10:12:56 AMAPASS
pat - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-01900 Electrical Rough-In5/24/20065/25/20065/25/2006 9:36:31 AMAPART
dave; Phone #: ###-#### Internet Inspection Request from: Darla Downs walls ok contractor will address dual switching for energy code
ELE06-01798 Electrical Rough-In5/24/20065/25/20065/25/2006 9:07:41 AMAPART
brian - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles temp wiring ok corr. for vision center low voltage support wires and cables remove old and abandoned cables, no cords allowed above ceilings, front restrms ok
ELE06-01850 Temporary Service5/24/20065/25/20065/25/2006 8:17:07 AMAFAIL
Don; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. 110.3(B) shall use 100 amp feeder to job shack called
ELE06-01807 Electrical Rough-In5/24/20065/25/20065/25/2006 7:44:53 AMAPART
Please call Greg to set up a early a.m inspection due to working midnights. Thanks! Greg= ###-####.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie partial u/g ok