ELE06-01825
| Temporary Service | 5/25/2006 | 5/25/2006 | 5/25/2006 4:58:34 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/25/2006 at 7:52:54 AM. Contact: ###-####. t/s o/h new ok
|
ELE06-00711
| Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 4:52:20 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 5/24/2006 at 2:27:23 PM. Contact: ###-####. com rm basement, 3rms elevator lobby dir office 2nd floor anop
|
ELE06-01142
| Final | 5/24/2006 | 5/25/2006 | 5/25/2006 2:19:38 PM | A | FAIL |
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr. fee due posted called 680.26(B)(1) shall bond all parts of metal (cover track)314.3 shall follow manufactures instructions for plastic box with metallic raceway, 110.3 shall not remove sealing washer from listed R/T emt fittings
|
ELE06-01919
| Electrical Rough-In | 5/25/2006 | 5/25/2006 | 5/25/2006 2:04:30 PM | P | PART |
|
|
melissa bierman ###-#### conference only
|
ELE06-01778
| Rough-In Permanent Service | 5/24/2006 | 5/25/2006 | 5/25/2006 12:18:58 PM | A | PASS |
|
|
Internet Inspection Request from: Melyne Davis r/i p/s u/g new ok
|
ELE06-01899
| Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 10:42:55 AM | A | PASS |
|
|
roger ###-#### walls ok no boxes shall be covered by wall finish called
|
ELE06-01892
| Permanent Service | 5/24/2006 | 5/25/2006 | 5/25/2006 10:13:18 AM | A | PASS |
|
|
pat - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec. ok
|
ELE06-01892
| Final | 5/25/2006 | 5/25/2006 | 5/25/2006 10:12:56 AM | A | PASS |
|
|
pat - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-01900
| Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 9:36:31 AM | A | PART |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Darla Downs walls ok contractor will address dual switching for energy code
|
ELE06-01798
| Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 9:07:41 AM | A | PART |
|
|
brian - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles temp wiring ok corr. for vision center low voltage support wires and cables remove old and abandoned cables, no cords allowed above ceilings, front restrms ok
|
ELE06-01850
| Temporary Service | 5/24/2006 | 5/25/2006 | 5/25/2006 8:17:07 AM | A | FAIL |
|
|
Don; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. 110.3(B) shall use 100 amp feeder to job shack called
|
ELE06-01807
| Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 7:44:53 AM | A | PART |
|
|
Please call Greg to set up a early a.m inspection due to working midnights. Thanks! Greg= ###-####.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie partial u/g ok
|