Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00215 INSP-Sprinkler Rough-in/Hydro5/25/20065/25/20065/25/2006 3:59:03 PMPPASS
According to Adam the above ground hydro test passed. It was witnessed by the general contractor. Test papers will need to be provided.
FIR06-00139 INSP-Sprinkler Rough-in/Hydro5/25/20065/25/20065/25/2006 3:58:25 PMPPASS
According to Adam the above ground hydro test passed. It was witnessed by the general contractor. Test papers will need to be provided.
BLD06-00600 FIRE-Final Inspection5/24/20065/25/20065/25/2006 3:51:57 PMPPART
A temporary occupancy was given until an audio/visual device needs to be added in the corridor that is within the scope work. This will require permits
FIR06-00247 INSP-Final Inspection5/25/20065/25/20065/25/2006 2:49:33 PMPFAIL
No real inspection was performed due to items found just walking around. Manual pull stations and the wall mounted a/v on the kitchen wall(facing dining) are mounted too high. Not all heights have been verified. Also the ceiling mounted a/v's are mounted above 10' which means reduced spacing is used. If, since spacing has not been checked yet, the a/v's are overspaced and the contractor wants to just increase the cd rating, resubmittals will be required. Mary was at this inspection as well and knows what is going on.
FIR06-00207 INSP-Sprinkler Rough-in/Hydro5/24/20065/25/20065/25/2006 2:35:32 PMPPASS
Need eschuesions then can be finaled.
FIR06-00208 INSP-Sprinkler Rough-in/Hydro5/24/20065/25/20065/25/2006 2:29:53 PMPFAIL
Provide hanger on relocated head immediatley outside of the new room, right above doors into room.
FIR06-00206 INSP-Sprinkler Rough-in/Hydro5/24/20065/25/20065/25/2006 2:17:57 PMPPASS
Rough-in passed.
FIR06-00387 INSP-Final Inspection5/23/20065/25/20065/25/2006 1:51:08 PMAFAIL
Could not do inspection since the wrong gas regulator had been installed and the pilot lights would not work.
FIR06-00293 INSP-Sprinkler Rough-in/Hydro5/23/20065/25/20065/25/2006 1:49:10 PMACANC
Phone #: ###-#### Contractor wanted to cancel
BLD05-03015 FIRE-Conference5/25/20065/25/20065/25/2006 11:52:20 AMPDONE
I issued a stop work order for all trades after finding fire alarm backboxes installed at project. No one was at the job site so I called the general contractor and spoke to him about the situation. I told him that I could lift the stop work order if the electrical contractor removed the parts of the fire alarm system that have been installed. Mary and Sam have been notified.
BLD06-00634 FIRE-Final Inspection5/25/20065/25/20065/25/2006 12:00:00 AMPCANC
kathy hanson; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wasnt ready