FIR06-00215
| INSP-Sprinkler Rough-in/Hydro | 5/25/2006 | 5/25/2006 | 5/25/2006 3:59:03 PM | P | PASS |
|
|
According to Adam the above ground hydro test passed. It was witnessed by the general contractor. Test papers will need to be provided.
|
FIR06-00139
| INSP-Sprinkler Rough-in/Hydro | 5/25/2006 | 5/25/2006 | 5/25/2006 3:58:25 PM | P | PASS |
|
|
According to Adam the above ground hydro test passed. It was witnessed by the general contractor. Test papers will need to be provided.
|
BLD06-00600
| FIRE-Final Inspection | 5/24/2006 | 5/25/2006 | 5/25/2006 3:51:57 PM | P | PART |
|
|
A temporary occupancy was given until an audio/visual device needs to be added in the corridor that is within the scope work. This will require permits
|
FIR06-00247
| INSP-Final Inspection | 5/25/2006 | 5/25/2006 | 5/25/2006 2:49:33 PM | P | FAIL |
|
|
No real inspection was performed due to items found just walking around. Manual pull stations and the wall mounted a/v on the kitchen wall(facing dining) are mounted too high. Not all heights have been verified. Also the ceiling mounted a/v's are mounted above 10' which means reduced spacing is used. If, since spacing has not been checked yet, the a/v's are overspaced and the contractor wants to just increase the cd rating, resubmittals will be required. Mary was at this inspection as well and knows what is going on.
|
FIR06-00207
| INSP-Sprinkler Rough-in/Hydro | 5/24/2006 | 5/25/2006 | 5/25/2006 2:35:32 PM | P | PASS |
|
|
Need eschuesions then can be finaled.
|
FIR06-00208
| INSP-Sprinkler Rough-in/Hydro | 5/24/2006 | 5/25/2006 | 5/25/2006 2:29:53 PM | P | FAIL |
|
|
Provide hanger on relocated head immediatley outside of the new room, right above doors into room.
|
FIR06-00206
| INSP-Sprinkler Rough-in/Hydro | 5/24/2006 | 5/25/2006 | 5/25/2006 2:17:57 PM | P | PASS |
|
|
Rough-in passed.
|
FIR06-00387
| INSP-Final Inspection | 5/23/2006 | 5/25/2006 | 5/25/2006 1:51:08 PM | A | FAIL |
|
|
Could not do inspection since the wrong gas regulator had been installed and the pilot lights would not work.
|
FIR06-00293
| INSP-Sprinkler Rough-in/Hydro | 5/23/2006 | 5/25/2006 | 5/25/2006 1:49:10 PM | A | CANC |
|
|
Phone #: ###-#### Contractor wanted to cancel
|
BLD05-03015
| FIRE-Conference | 5/25/2006 | 5/25/2006 | 5/25/2006 11:52:20 AM | P | DONE |
|
|
I issued a stop work order for all trades after finding fire alarm backboxes installed at project. No one was at the job site so I called the general contractor and spoke to him about the situation. I told him that I could lift the stop work order if the electrical contractor removed the parts of the fire alarm system that have been installed. Mary and Sam have been notified.
|
BLD06-00634
| FIRE-Final Inspection | 5/25/2006 | 5/25/2006 | 5/25/2006 12:00:00 AM | P | CANC |
|
|
kathy hanson; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wasnt ready
|