Inspections for the day of: Friday, May 25, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01822 Electrical Rough-In5/25/20075/25/20075/25/2007 2:55:56 PMPPASS
trent - southwest corner walls ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE07-01718 Electrical Rough-In5/25/20075/25/20075/25/2007 2:23:59 PMPPART
butch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added conference for p/s, and comm. building wiring, r/i for storage room ok needs too remove SER feeder to subpanel
ELE07-01718 Conference5/25/20075/25/20075/25/2007 2:22:23 PMPDONE
butch ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
met contr, told him about p/s, grounding, no SER cable for comm. work, and shall not use ampacities table for dwelling for comm. work
ELE06-04140 Final5/25/20075/25/20075/25/2007 1:40:24 PMPFAIL
kelly - call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called 210.52 (D) needs recept within 3ft of sink
ELE07-01393 Final5/25/20075/25/20075/25/2007 12:51:58 PMPPASS
Scheduled by a contractor via Hello! on 5/25/2007 at 7:22:39 AM. Contact: ###-####. ok
ELE07-01340 Electrical Rough-In5/25/20075/25/20075/25/2007 12:16:58 PMPPART
lloyd - partial ceiling grid ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok anop
ELE07-01884 Final5/24/20075/25/20075/25/2007 10:27:58 AMACANC
Darrell; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
see added r/i p/s
ELE07-01884 Rough-In Permanent Service5/25/20075/25/20075/25/2007 10:27:27 AMAPASS
Darrell; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
r/i shop and u/g ok
ELE07-01341 Permanent Service5/24/20075/25/20075/25/2007 10:01:33 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer corr called note partial correction only 408.4 be specific , 312.5 conn for GEC, 110.26(F)(1) clearence for subpanel, BCC no violation retained
ELE07-00813 Final5/24/20075/25/20075/25/2007 9:21:49 AMAPASS
Audrey; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
ELE07-01260 Rough-In Permanent Service5/23/20075/25/20075/25/2007 9:01:50 AMAPASS
J-man on site gene ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
r/i p/s u/g new ok
ELE07-01261 Rough-In Permanent Service5/24/20075/25/20075/25/2007 9:01:22 AMAPASS
On site journeyman - Gene ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
r/i p/s u/g new ok